Permit Information
Permit NumberFIR08-00006
StatusFinaled
Name HIGH COUNTRY ALARM INC
Site Address 7250 W POPLAR ST
Project NameCHATEAU DE BOISE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to establish compliance with the International Fire Alarm Code - Chapter 907 requirements due to the replace of the existing fire alarm control panel. The work was completed prior to the permit issuance and a new Silent Knight 5208 fire alarm control panel was installed replacing the previous panel that was described to have a timer module defect and outdated. The system requires and mentions that new compatible automatic smoke detectors were installed with the new FACP. No building permit is associated with this permit. (Stand Alone)

07-23-08 SCOPE MODIFICATION: The installing contractor has changed to High Country Alarms. The new installer has not started work without a permit.
NOTE TO INSPECTOR: The original fire alarm system was designed and installed to the 1979 edition of the UBC and related codes. Because the original panel is not working, this is not considered a "system replacement", but just a panel replacement. At that time of installation, there was not a distinction between R1 and R2 occupancies. Based on the original code, this would fall under an R2 occupancy classification now.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/9/200812/11/200812/11/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/8/200812/9/200812/9/2008PFAIL
DetailsTroy Cobbley
All of the smoke detectors and manual pull stations have been tested including phone line troubles and battery tourbles. Phone line one appears to have a problem. Audio/visuals need to be tested as well as end of line voltage. A map at the facp is required.
INSP-Final Inspection12/5/200812/8/200812/8/2008PFAIL
DetailsTroy Cobbley
This inspection turned into a first floor walk through/conference. All of the first floor wing smoke detectors are overspaced, a smoke detector in the common are needs to be relocated closer to the double doors to the wing and visuals are overspaced. Locations are marked on the plans. No testing was performed.
FIR-Aging Inspection11/24/200811/24/200811/26/2008 NR
DetailsTroy Cobbley
Per Darcy the work for this project is in progress.