Permit NumberFIR08-00068
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 252 E FRONT ST
Project NameID WATER CENTER-PA2 BLDG
Customer Number 
ePlanReview 
Description
overheadWork Scope: Over Head Only
Modify the existing wet pipe sprinkler system with in this existing Office bldg. to accommodate a new ceiling layout. The scope includes adding 110 new recessed pendant heads. The existing upright protect will remain as is. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to permit BLD07-03026. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20087/21/20087/21/2008APASS
DetailsForrest France
Required corrections verified for compliance, fire sprinkler permit finaled.
INSP-Final Inspection7/17/20087/18/20087/18/2008AFAIL
DetailsForrest France
See annotations on stamped plan set for locations in need of repair including one painted upright head, one pendent blocked by an adjacent light fixture at the women's locker room, one missing escutcheon, two heads blocked by insulation at the ceiling in the OTS storage room.
INSP-Sprinkler Rough-in6/27/20086/30/20086/30/2008AFAIL
DetailsForrest France
See annotations on plan for areas in need of revision including missing head coverage at a storage room, two missing armover hangers, three painted heads to be replaced, and one pendent cut too high. Remainder of overhead system modifications are good for cover at the drop ceilings.
INSP-Sprinkler Rough-in6/26/20086/26/20086/26/2008PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in5/1/20085/2/20085/2/2008APART
DetailsForrest France
Inspection completed for hard lid areas finished to date, okayed for cover storage rooms 129A, 108A, work room 128, mens restrooms 147 and 148, womens restroom 145. NOTE: no approval for cover at womens restroom 149 due to missing hanger at the arm-over to the pendent head, see stamped plan set for annotations.
INSP-Sprinkler Rough-in4/21/20084/21/20084/22/2008PPASS
DetailsTroy Cobbley
See the city approved plans for new areas above hard lids that are marked ok to cover.
INSP-Sprinkler Rough-in/Hydro4/16/20084/16/20084/16/2008PNR
DetailsForrest France
Work is not completed for inspection per contractor as requested.