INSP-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 | A | PASS |
Forrest France
|
|
|
Fire alarm permit approved for final.
|
INSP-Alarm Testing | 2/24/2009 | 2/24/2009 | 2/24/2009 | P | DONE |
Troy Cobbley
|
|
|
TRASH ROOM SMOKE DETECTOR Phone #: ###-#### Internet Inspection Request from: Robert Gobler
|
INSP-Alarm Testing | 2/24/2009 | 2/24/2009 | 2/24/2009 | A | DONE |
Scott Arellano
|
|
|
Tested smoke door operation at exterior wall, located in garbage room. Tested satisfactory.
|
INSP-Final Inspection | 2/20/2009 | 2/20/2009 | 2/20/2009 | P | PART |
Forrest France
|
|
|
Remainder of fire alarm testing completed satisfactory, noted corrections have been finished, elevator, FACP, balance of notification, etc. all tested okay. Final pending one SD for door release at the trash room level P1 to be tested (missing power to overhead door), and provision of resubmittal plans for field modifications including added ID detectors, hoistway devices, deleted points, accurate matrix, etc. as discussed.
|
INSP-Alarm Testing | 2/11/2009 | 2/12/2009 | 2/12/2009 | A | PART |
Forrest France
|
|
|
Discussed plan resubmittals due to modifications including 13 added SD for dampers in the common corridors, added heat and smoke detectors in the elevator hoistway, relay for the mag locks at the main lobby doors, changes in the matrix for unused CR at the elevator smoke doors. Walkthrough for the basement level parking garage completed-noted one overspaced area at a handicap accessible parking space. Discussed project inspection schedule, also need to provide list of signals recieved during pre-testing.
|
FIR-Aging Inspection | 5/30/2008 | 5/30/2008 | 5/30/2008 | | DONE |
Forrest France
|
|
|
Under construction, work in progress.
|