Permit Information
Permit NumberFIR08-00121
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 3423 S FEDERAL WAY
Project NameRoss Dress for Less
Customer Number 
ePlanReview 
Description
6/20/08 PLAN MODIFICATION: To install two relays for two delayed egress doors that were not part of the original scope of work.This fire alarm permit is to install a new manual and partial automatic fire alarm system. Work includes sprinkler monitoring, manual pull stations, selected area coverage smoke detection, duct smoke detectors for HVAC shut down, complete a/v notification appliance coverage, and remote annunciator.

The associated building permit, BLD07-01188, is To construct a new 25,925 square foot, one story retail store and related site improvements. This building is constructed of masonry exterior walls and steel roof joists and support columns, with metal roof deck and single ply roofing system. This building is fully fire sprinkled. The sprinklers are used for area increase. This building was reviewed as nonseparated uses. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20086/25/20086/25/2008APASS
DetailsForrest France
Remainder of items on the correction notice verified for compliance, final fire alarm inspection passed, permit finaled.
INSP-Final Inspection6/23/20086/23/20086/23/2008PFAIL
DetailsForrest France
See five item correction notice for defficient items.
INSP-Alarm Testing6/20/20086/23/20086/23/2008AFAIL
DetailsForrest France
Provide map at the FACP, missing signage at the door to the fire alarm panel room, provide visual notification for the women's fitting room vestibule per plan review annotations, door mag locks at the south and north exits are not installed at this time for functional testing of interconnection to the fire alarm system, noted RTU #3 duct detector is not operational at the factory installed supply side (return side is okay), addresses at RTU # 1 amendend while on site, will sign record of completion forms when c/n items are finished, remainder of fire alarm work test passed including signal monitoring.
INSP-Alarm Testing3/17/20083/17/20083/17/2008AFAIL
DetailsForrest France
See on site correction notice regarding off site monitoring requirements.
INSP-Conference3/12/20083/14/20083/14/2008PFAIL
DetailsForrest France
Per contractor, the required off site monitoring account has not been initiated. Final system testing and acceptance cannot be completed until monitoring is on line-see fire code review note #2 for details. Prior to final inspection the NFPA 72 "Inspection and Testing Form" fig. 10.6.2.3 must be completed including a copy of the supervising station signals report.