Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR08-00151
StatusFinaled
Name ALARM SYSTEMS INTEGRATION INC
Site Address 1880 W JUDITH LN
Project Nameshell
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a fire alarm System to monitor the fire sprinkler system and to perform the required functions for the new elevator.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/20/20088/20/20088/20/2008PPASS
DetailsForrest France
items on correction notice verified for completion, fire alarm permit finaled.
INSP-Alarm Testing8/19/20088/19/20088/19/2008AFAIL
DetailsForrest France
Fire alarm system field testing completed however reciept of signals could not be verifed due to lack of account monitoring set up, need to complete NFPA 72 inspection and testing forms including a list of singals prior to final, provide plans reflecting field changes including deleted notification devices, deleted elevator hoistway detectors, changed battery to 18 AH, provide accurate map at the panel, post signage at the door to the FACP room, change descriptor at riser #2 to read "antifreeze system", need to test main door mag lock interconnection to the fire alarm when finished.
INSP-Alarm Testing8/15/20088/18/20088/18/2008PFAIL
DetailsForrest France
Elevator is not yet completed to verify fire alarm interconnections and functionality.
FIR-Aging Inspection6/20/20086/20/20086/20/2008 DONE
DetailsForrest France
wip