Permit Information
Permit NumberFIR08-00180
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4719 S MARKET ST Unit: 103
Project NameMARKET STREET WAREHOUSE
Customer Number 
ePlanReview 
Description
The data has been moved to a Word document attached to this case.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/2/20086/2/20086/2/2008PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection5/30/20086/3/20086/2/2008PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 5/30/2008 at 4:48:42 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 2 2008 7:49AM.
INSP-Final Inspection5/29/20085/30/20085/30/2008ADEFR
DetailsForrest France
INSP-Final Inspection5/28/20085/29/20085/29/2008ANR
DetailsForrest France
Scheduled by a contractor via Hello! on 5/28/2008 at 3:15:38 PM. Contact: ###-####.
INSP-Final Inspection5/27/20085/28/20085/28/2008PCANC
DetailsForrest France
rod Phone #: ###-#### Overbooked
INSP-Sprinkler Rough-in/Hydro5/6/20085/7/20085/7/2008APART
DetailsForrest France
OH install at the east office area first and second floors for rooms and areas completed to date are okay for cover, no access at one hallway due to flooring work underway, missing heads at two utility rooms 2nd floor, verified corrections are finished at the entry vestibule, need access to verify coverage at the concealed combustible spaces under the stairway at two locations. Hydrostatic testing for the new 10"supply main at the warehouse completed satisfactory, also discussed seismic bracing issues.
INSP-Sprinkler Rough-in/Hydro5/5/20085/6/20085/7/2008PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in/Hydro4/29/20084/29/20084/29/2008ANR
DetailsForrest France
New supply line pipe hydrostatic test is not ready for inspection due to leakage per contractor, also okayed areas as red-lined on approved plan set at the front office entry hard lids-noted three ret. straps to be attatched and one head to be relocated for correct min. spacing requirements.
INSP-Sprinkler Rough-in/Hydro4/25/20084/28/20084/28/2008PFAIL
DetailsForrest France
Hydrostatic testing for the new 10" supply line failed due to pressure loss at the guage and visible leakage at OS&Y isolation valves, also noted system static is approx. 165 psi which will necessitate testing in excess of 200 psi to meet NFPA requirements.
INSP-Sprinkler Rough-in/Hydro4/8/20084/9/20084/9/2008PFAIL
DetailsForrest France
Inspection for cover at the womens and mens restrooms for the office area east side failed due to two pendent sprinkler heads which do not meet obstruction tables per NFPA 13.