INSP-Final Inspection | 6/2/2008 | 6/3/2008 | 6/3/2008 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 5/29/2008 | 5/29/2008 | 5/29/2008 | P | FAIL |
Troy Cobbley
|
|
|
The north duct smoke detector in the Billiards store did not shut down the hvac unit as per chapter 6 of the IMC. The other duct smoke detectors operated correctly.
|
INSP-Conference | 4/8/2008 | 4/9/2008 | 4/9/2008 | A | DONE |
Troy Cobbley
|
|
|
The first time I stopped at the project the facp was not dialing out to the monitoring station. I returned acouple of hours later and the problem, wiring related, had been fixed. I verified signals with the monitoring station. I also pointed out that the manual pull station was mounted too high and the technicians had lowered at by the time I arrived for my second inspection. I notified sam rogers and mark sentenno.
|