Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR08-00255
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 3101 W CASSIA ST
Project NameSOUTH JUNIOR HIGH SCHOOL
Customer Number 
ePlanReview 
Description
Protex submitted a early start fire alarm request. As per Sam Roger, Early start was granted. This fire alarm permit is to install a new fire alarm system in a new building. System to include HVAC, fire/smoke damper monitoring, sprinkler system monitoring, elevator recall functions, smoke detectors in the corridors, and voice evacuation in auditorium areas.

Associated building permit for reference:
BLD07-00007 (SOUTH JUNIOR HIGH SCHOOL) To construct a 140, 546 sq. ft. two story fully fire sprinkled middle school building. Other work includes all site work, paving and landscaping per approved plans and attachments. Note: This project has phases which include demo of the existing school and a new amphitheater which will be done under separate permits. Fire sprinklers used for area. Building has 2 hour fire walls dividing the building into three separate buildings of Type IIA and IIB construction. Total area 1st floor 90,786 sq. ft. 2nd floor 49,760 sq. ft.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/15/20094/15/20094/15/2009PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection10/22/200810/24/200810/24/2008PPART
DetailsForrest France
All corrections were made. Fire alarm testing complete. Can not final until we have copys of NFPA 72 and map at anunciator. KR
INSP-Final Inspection10/14/200810/14/200810/14/2008PPART
DetailsForrest France
One fire damper in up stairs storage area behind stage was not connected to fire alarm system, a module will be added to smoke detectors. All fire alarm testing completed in assembly area except as noted above. NFPA inspection report must be completed before complete final. KR
INSP-Final Inspection10/9/200810/13/200810/13/2008AFAIL
DetailsForrest France
See red lined notes on plans at area A for locations in need of revision including horn and speaker/strobe devices.
INSP-Final Inspection8/11/20088/15/20088/15/2008APART
DetailsForrest France
See notice of violation paper work for corrections completed.KR
INSP-Alarm Testing8/11/20088/11/20088/12/2008APART
DetailsForrest France
Fire dampers passed testing with the exception of one damper at corridor B01-see plans for location, some items on c/n repaired. Items remaining include EOL voltage testing, provide list of signals recieved, area "A" auditorium is not complete including voice evac., two elevators are not finished, kitchen hood interconnect needs tested, noted two supervisory signals at the FACP due to elevator power loss, need to test nac batteries, provide NFPA 72 Record of Completion documents at final inspection.
INSP-Final Inspection8/6/20088/8/20088/8/2008APART
DetailsForrest France
Refer to red-lines on approved plan set for noted deficiencies and remainder of work to be completed and inspected.
INSP-Final Inspection8/6/20088/6/20088/6/2008PFAIL
DetailsForrest France
See red line notes on plans for deficiencies and areas tested today per site visit by K. Roule.
INSP-Final Inspection7/31/20088/5/20088/5/2008APART
DetailsForrest France
See red line notes on approved plan set for continuation of initiation devices tested today and locations in need of correction.
INSP-Final Inspection7/31/20088/4/20088/4/2008APART
DetailsForrest France
See red-lines on plans for locations of initiation devices tested today and areas in need of adjustment.
INSP-Final Inspection7/29/20088/1/20088/1/2008APART
DetailsForrest France
Manual pull stations and notification devices tested today per K. Roule, see plans for locations in need of adjustment.
INSP-Final Inspection7/30/20087/31/20087/31/2008AFAIL
DetailsForrest France
Walkthrough of classroom wings areas J,I, E and F completed today- noted items on plans in need of correction including smoke detectors to be relocated due to proximity to HVAC registers, spacing or cd adjustment at some av's, pull stations at two locations, noted minor floor plan changes, initiation devices not tested due to missing phone lines.
INSP-Final Inspection3/27/20093/27/2009 P 
DetailsForrest France
Contact Rafe Phone#: ###-####