INSP-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 | P | PASS |
Forrest France
|
|
|
AM fire alarm notification appliance testing completed acceptable, field modifications noted on as-built plans okayed, corrections per last inspection repaired, permit finaled. NOTE: mag locks at access control doors did not appear to drop out on fire alarm condition per IFC requirements-not included in the scope of this permit work.
|
INSP-Final Inspection | 6/16/2008 | 6/17/2008 | 6/17/2008 | A | FAIL |
Troy Cobbley
|
|
|
The first audio/visual I looked at has not been set at the correct candella. Also when we activated the audio/visual devices the audio was not in sync or even in temporal. The visuals started flashing at different rates or not at all. Brian said it appears that the NAC panel has failed. Testing was stopped.
|