Permit Information
Permit NumberFIR08-00266
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 930 N CLOVERDALE RD
Project NameIDAHO KOREAN PRESBYTERIAN CHUR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new manual system and HVAC system monitoring in an existing building and extend it into the building addition.

BLD07-02123 (Idaho Korean Presbyterian Church - Addition) To add approximately 5,530 square feet of additional floor area to an existing 1,840 square feet, A-3, assembly building. Work included in this permit is to add three new educational class rooms, a 3,600 square feet sanctuary with fixed seating, construction of two new accessible restrooms, and a 200 square feet warming kitchen. NOTE: A two hour fire barrier will be used to separate the A-3 fire areas and maintain an occupant load below three hundred.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/8/200810/8/200810/8/2008APASS
DetailsTroy Cobbley
fire alarm testing passed previous inpection by Troy Cobbley. KR.
INSP-Alarm Testing9/19/20089/19/20089/19/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/11/20089/17/20089/17/2008PFAIL
DetailsTroy Cobbley
Everything tested ok except the strobe in the mens restroom did not function, the sample tubes in the duct smoke detectors are not in the correct holes and the exhaust tubes need to be shortened per the installation guide. Also the strobes do not stop flashing when the horns are silenced as required per NFPA 72.
FIR-Aging Inspection7/31/20087/31/20088/1/2008 NR
DetailsTroy Cobbley
Work is in progress