Permit NumberFIR08-00287
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 1301 N ORCHARD ST
Project NameCENTER POINTE ONE / orchard pl
Customer Number 
ePlanReview 
Description
This permit is to install a new NAC panel, new A/V devices and three new duct detectors in a remodel and addition.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/7/20097/8/20097/8/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/29/20096/30/20096/30/2009AFAIL
DetailsTroy Cobbley
The devices at the new riser at the east side of the building functioned correctly. The new devices in the elevator did not function correctly. An inspection will need to be resceduled with the elevator contractor.
INSP-Alarm Testing3/2/20093/3/20093/3/2009PPASS
DetailsTroy Cobbley
The fire alarm for the Corrections area is now complete.
INSP-Alarm Testing2/26/20092/26/20092/27/2009PFAIL
DetailsTroy Cobbley
This inspection was for the Corrections tenant expansion into the new area of the first floor. NAC circuit #4 did not meet the minimum 21.6 volt requirement at the end of line. Caps were missing from the end of the sample tubes for the two duct smoke detectors tested. There have been significant changes to the notification circuits and resubmittals will be required prior to a final inspection and sign off.
FIR-Aging Inspection8/4/20088/4/20088/4/2008 NR
DetailsTroy Cobbley
work is in progress