INSP-Final Inspection | 9/30/2008 | 9/30/2008 | 9/30/2008 | P | PASS |
Forrest France
|
|
|
Correction notice items have been repaired, two missing 401 canopies installed while on site, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 8/11/2008 | 8/12/2008 | 8/12/2008 | A | FAIL |
Forrest France
|
|
|
See annotations on plan set for items in need of correction including spacing at pendent heads in the womens restroom, one painted head above the stairs 2nd floor, spacing at two heads adjacent to the elevator lobby, noted two heads at the first floor with excessive loading. Relocated heads at the kitchen area are okay for cover.
|