INSP-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm inspection completed. Candella in living room and family room were changed to 75cd. Inspection and completion forms were signed and will be faxed to PDS fire on 7/7/08. KR
|
INSP-Final Inspection | 7/1/2008 | 7/1/2008 | 7/1/2008 | P | FAIL |
Forrest France
|
|
|
NFPA 72 forms, letter of completion were not filled out. No testing performed on smoke detectors, contractor did not have canned smoke. sprinkler flow switch and tamper were tested. No other testing completed.KR
|
INSP-Alarm Testing | 6/27/2008 | 6/30/2008 | 6/30/2008 | P | CANC |
Forrest France
|
|
|
Talked with David and let him know that the sprinkler permit also needs to be called in for the fire alarm testing. He will call in both permits tomorrow for finals.KR
|