INSP-Final Inspection | 1/14/2009 | 1/16/2009 | 1/16/2009 | A | PASS |
Forrest France
|
|
|
Final fire sprinkler inspection and acceptance testing completed satisfactory, permit finaled.
|
INSP-Sprinkler Rough-in | 1/15/2009 | 1/15/2009 | 1/15/2009 | P | PART |
Forrest France
|
|
|
Correction notice items per last inspection are finished, verified resubmitted plans for field changes, rough-in passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/14/2009 | 1/15/2009 | 1/15/2009 | A | PART |
Forrest France
|
|
|
OH hydrostatic testing completed satisfactory.
|
INSP-Final Inspection | 1/14/2009 | 1/15/2009 | 1/14/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 1/14/2009 at 11:08:00 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 14 2009 11:25AM.
|
INSP-Sprinkler Rough-in/Hydro | 12/30/2008 | 12/31/2008 | 12/31/2008 | P | FAIL |
Forrest France
|
|
|
Approved plan set on site does not match floorplan or actual installation including heads and piping beneath three mezzanines, added mech. tees and uprights, noted one work area overspaced beyond 130 ft2, missing forward flow appuratus at the riser, need PRV due to grid system, hydrostatic test postponed until changes are approved.
|
INSP-Sprinkler Rough-in/Hydro | 12/29/2008 | 12/30/2008 | 12/30/2008 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled
|
INSP-Supply line flush | 7/7/2008 | 7/10/2008 | 7/10/2008 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed acceptable.
|
INSP-Supply line flush | 7/2/2008 | 7/8/2008 | 7/8/2008 | A | PART |
Forrest France
|
|
|
Field inspection was intended for an UG hydrostatic test. Hydro completed satisfactory-testing passed.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | PART |
Forrest France
|
|
|
UG fire supply line installation is approved for bury.
|
INSP-Supply line flush | 7/3/2008 | 7/7/2008 | 7/7/2008 | P | NR |
Forrest France
|
|
|
tony/brian ###-#### Note: 1:00 Phone #: ###-#### Inspection rescheduled per conversation with contractor.
|
INSP-Supply line flush | 7/1/2008 | 7/7/2008 | 7/2/2008 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 7/1/2008 at 11:35:54 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 2 2008 7:16AM.
|