Permit Information
Permit NumberFIR08-00373
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 3733 W QUAIL HOLLOW DR
Project Name 
Customer Number 
ePlanReview 
Description
FIR Sprinkler Scope: Install a new 13D modified fire sprinkler system through out the single story single family dwelling with a finished basement to a single row of dry sidewall sprinklers along the wall common to attached garages and the living space. System shall be equipped with an alarm initiating device and an outside alarm. The system will be supplied from an existing 1” poly dedicated fire line. (by others) All fire sprinkler work and related, which includes a single dedicated service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to BLD08-00373.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200810/13/200810/13/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/10/200810/10/200810/13/2008PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 10/10/2008 at 8:38:50 AM. Contact: ###-####.
INSP-Sprinkler Rough-in/Hydro7/9/20087/9/20087/9/2008PPART
DetailsTroy Cobbley
Changes made per last inspection. OK to cover. KR
INSP-Sprinkler Rough-in/Hydro7/8/20087/8/20087/8/2008PFAIL
DetailsTroy Cobbley
As-builts need to be provided showing the pipe route changes. See the city approved plans for locations where sprinkler pendants are located too close, too far off of walls and where no sprinkler protection has been provided. One location needs the tenting improved.