Permit Information
Permit NumberFIR08-00388
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3395 S FEDERAL WAY
Project NameWALGREENS
Customer Number 
ePlanReview 
Description
overhead FIR OH Scope:
Beginning from a 6” supply located with the 1 hour rated riser room located at the NE corner of the building, install a 4” vertical wet riser and a wet pipe system to serve through out the heated areas. A anti-freeze loop / system will serve the entry vestibule and sign tower. Any future rack plans shall be submitted under a separate permit. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/200810/17/200810/17/2008APASS
DetailsForrest France
Correction notice items verified for completion, fire sprinkler permit finaled.
INSP-Final Inspection10/13/200810/14/200810/14/2008AFAIL
DetailsForrest France
Inspection failed due to several items including one painted head at the electrical room, leaking pendent at the pharmacy area, dry pendent heads are not yet installed at the coolers, missing escutcheon at the staff restroom, provide correct pipe hanger at the outside storage locker, need as-builts for field mods, PIV tamper is not correcly adjusted, waterflow switch needs adjustment, provide pitot guage for forward flow testing, need main control signage at the riser #1 and #2 shutoff valves.
INSP-Sprinkler Rough-in/Hydro9/18/20089/19/20089/19/2008APART
DetailsForrest France
OH hydrostatic testing including the wet and antifreeze loop system passed, verified c/n items, noted concealed heads at the restrooms may be obstructed by adjacent surface mounted light fixtures when installed.
INSP-Sprinkler Rough-in8/22/20088/25/20088/25/2008AFAIL
DetailsForrest France
SW heads at the sign tower antifreeze loop are overspaced and below max. listed distance from the ceiling, noted several missing retaining straps at numerous locations including mains and branch lines-somel installed while on site, combustibles above the restrooms must be removed or protection provided, waiting area drops are 3/4"-plan shows 1/2" heads, four upright heads at the stock room are obstructed by beams or exceed min. spacing.