ePlanReview 
Description
10/30/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted As-Built for approval. The revisions have been noted as Rev #4 and dated 10/02/08.
10/22/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition, several pipe size changes were made in order to assure the required flow (gpm) as designed.
09/12/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition to the pump, the contractor changed the ½” riser supply sections of piping to 1”. These revisions were noted on the plans as Revision #3 and dated 09-08-08. Revised FIR Sprinkler Scope: These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition to the pump, the contractor changed the ½” riser supply sections of piping to 1”. These revisions were noted on the plans as Revision #3 and dated 09-08-08. FIR Sprinkler Scope: Install a new 13D approved multi purpose piping system (Uponor , Wirsbo ) fire sprinkler system through out the two story single family dwelling to include a single row of side wall heads in the garage along the common. The system will be supplied from a 1” poly line. (by others) All fire sprinkler work shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to BLD08-00813.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/200810/31/200810/31/2008PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in9/16/20089/16/20089/17/2008PPART
DetailsTroy Cobbley
The bucket test passed. The two head area flowed 31 gallons and the single head area flowed 22 gallons. I gave the ok to cover the piping with the condition that as-built plans and hydraulic calculations are re-submitted to the city. This is due to the interconnecting piping to and between the four manifolds, as installed, does not match the city approved plans.
INSP-Sprinkler Rough-in/Hydro9/12/20089/15/20089/15/2008AFAIL
DetailsTroy Cobbley
The updated plans were not on site but Sam Rogers and I went ahead and conducted the single and the double head flow verifications. The single head test passed in both the single head remote area and when just a single head was flowed in the two head area. But when the two head test was performed not enought water was put out. Infact not enough water was available when measured right at the pump. No rough-in inspection of the piping has been performed yet.
INSP-Sprinkler Rough-in8/28/20088/29/20088/29/2008AFAIL
DetailsTroy Cobbley
The plans have not been resubmitted showing the additional piping and the tenting was not complete. No inspection was performed though I did stop at the job site.
INSP-Sprinkler Rough-in/Hydro8/27/20088/28/20088/28/2008AFAIL
DetailsTroy Cobbley
The single head test barely made the 18gpm requirement and the 26.6gpm requirement for the two heads failed. The plans will have to be resubmitted if changes are made that effect piping or hydraulic calculations. Also the piping had not been tented yet.
INSP-Sprinkler Rough-in/Hydro8/26/20088/27/20088/27/2008PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/26/2008 at 1:29:31 PM. Contact: ###-####. Inspection cancelled from web by: Alexandra Rahn