INSP-Final Inspection | 6/17/2008 | 6/18/2008 | 6/18/2008 | A | PASS |
Forrest France
|
|
|
Required corrections verified for completion, fire alarm permit finaled.
|
INSP-Final Inspection | 6/17/2008 | 6/17/2008 | 6/17/2008 | P | PART |
Forrest France
|
|
|
Final pending correction of the descriptors at the FACP for three manual pull stations.
|
INSP-Final Inspection | 6/16/2008 | 6/17/2008 | 6/17/2008 | A | FAIL |
Forrest France
|
|
|
Repair work and device adjustments are not yet finished, inspection rescheduled.
|
INSP-Final Inspection | 6/13/2008 | 6/16/2008 | 6/16/2008 | P | FAIL |
Forrest France
|
|
|
Noted wall mounted notification appliances at six locations are below the min. height AFF per NFPA 72-see fire code review notes item #20, one ceiling mounted a/v needs to be installed per plan, remainder of installation appears acceptable however no functional testing performed due to devices to be relocated/adjusted.
|
INSP-Sprinkler Rough-in/Hydro | 6/16/2008 | 6/17/2008 | 6/16/2008 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 6/13/2008 | 6/16/2008 | 6/13/2008 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|