Permit Information
Permit NumberFIR08-00429
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1116 N COLE RD
Project NameBOISE RAQUET AND SWIM CLUB
Customer Number 
ePlanReview 
Description
Revised FIR OH Scope:
The fire sprinkler system was modified in the field in include coverage (8 additional QR heads) at the mezzanine which was added during construction. This revision was noted as Rev A, and dated 09/08/08 FIR OH Scope:
Beginning from an existing 6” supply located with the 1 hour rated riser room located at the SE corner of the building, install a 3” vertical wet riser to serve through out the entire structure including the area beneath the mezzanine. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00664 & UG permit FIR08-00354.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200810/14/200810/14/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/13/200810/13/200810/13/2008PFAIL
DetailsTroy Cobbley
The project is not ready for a final yet.
INSP-Sprinkler Rough-in/Hydro10/10/200810/13/200810/13/2008APASS
DetailsTroy Cobbley
The overhead hydro, underground hydros & fdc flush passed
INSP-Sprinkler Rough-in/Hydro10/8/200810/9/200810/9/2008PCANC
DetailsTroy Cobbley
Note: FDC Flush Phone #: ###-####.
INSP-Sprinkler Rough-in/Hydro10/6/200810/7/200810/7/2008ADONE
DetailsTroy Cobbley
Under ground flush completed. KR
INSP-Sprinkler Rough-in10/6/200810/7/200810/7/2008ADONE
DetailsTroy Cobbley
Remaining areas per Troys last inspection can be covered.KR
INSP-Sprinkler Rough-in9/29/20089/30/20089/30/2008APASS
DetailsTroy Cobbley
The underground piping for the remote FDC and the hose station can be covered except for both ends since thrust blocks, drains and vaults had not been installed yet. As-built plans need to be submitted showing the the positions of the two lines being switched and the remote hose station being relocated to the south.
INSP-Sprinkler Rough-in/Hydro9/24/20089/24/20089/24/2008PPASS
DetailsTroy Cobbley
The underground hydro test passed.
INSP-Sprinkler Rough-in9/15/20089/15/20089/15/2008PPASS
DetailsTroy Cobbley
The piping in the mezzanine can be covered. An as-built has been provided showing the extension of the mezzanine and the additional sprinkler protection.
INSP-Sprinkler Rough-in/Hydro8/25/20088/25/20088/25/2008PPART
DetailsForrest France
OH inspection for the court area mains and branchlines only completed today-the lower mezzanine piping is not yet installed, noted one missing EQ brace at the NW corner-location circled on plans, noted high temp. heads in place at the vicinity of the unit heaters, riser is not built.