INSP-Final Inspection | 8/14/2008 | 8/15/2008 | 8/15/2008 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 | P | NR |
Forrest France
|
|
|
Final pending as-built plans for heads relocated in the corridor and tile/escutcheons at all areas.
|
INSP-Sprinkler Rough-in | 8/7/2008 | 8/8/2008 | 8/8/2008 | A | PART |
Forrest France
|
|
|
2nd floor overhead work at the classrooms is approved for cover, noted modifications at the corridor to be indicated on as-built plans per discussion with the designer, basement area is missing five escutcheons at pendent heads.
|
INSP-Sprinkler Rough-in | 8/5/2008 | 8/6/2008 | 8/6/2008 | A | NH |
Forrest France
|
|
|
This is rough to cover for the 2nd fl. Plans are on site. Brian D is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus ****NOTE: Wrong permit number request, this permit is for basement work in the adjacent building.
|
INSP-Sprinkler Rough-in | 7/28/2008 | 7/29/2008 | 7/29/2008 | A | PART |
Forrest France
|
|
|
Reinspection for the basement level computer lab room passed rough-in, okay for cover at the drop ceilings.
|
INSP-Sprinkler Rough-in | 7/21/2008 | 7/22/2008 | 7/22/2008 | A | FAIL |
Forrest France
|
|
|
Field installation does not match approved plans including layout at the east side rooms, added head due to ceiling height change at the west side, contractor has installed 3/4 pendent heads despite approved drawings indicating 1/2 to be used, also lacking coverage for exposed combustible construction above the drop ceiling, corner adjacent to the south exit door is unprotected, provide accurate drawings prior to next inspection, ceiling cover is not approved at this time.
|