Permit Information
Permit NumberFIR08-00460
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 720 E PARK BLVD
Project NameMK PLAZA - 4TH FLR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add two new NAC panels and add/relocate notification devices in the tenant space to comply with current code requirements. There are no initiating devices associated with this permit scope.
Associated building permit: BLD08-00703 (4th FLOOR 1-HOUR CORRIDOR SYSTEM UPGRADE) A safe exiting system shall be maintained during the construction phase. Exit paths to be kept clear of debris and not used to store staging materials. This building is not sprinklered per 1973 UBC when constructed. Work includes select demolition; construction of 1-hour fire partition walls to create 1-hour corridor and separate elevator lobby from corridor; install listed & labeled, 20 minute fire rated, "S" labeled smoke-draft control, self closing with listed hardware door/frame assemblies at all openings into corridor except doors to existing stair enclosures; modify ceiling grid, mechanical, electrical, plumbing, alarm, exit signage / emergency illumination and finishes. This rated exit corridor is being installed per Sec.1015.2, exception #1 for exit separation between existing stair enclosures and to delete existing 2-hour horizontal exit installed under previous permit to provide separation. All per approved plans, notes on plans and attached plan review conditions of all plan reviewing agencies. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/3/20093/5/20093/5/2009APASS
DetailsForrest France
Noted correction items verified for completion, final fire alarm testing passed, permit finaled.
INSP-Final Inspection3/2/20093/4/20093/3/2009ADEFR
DetailsForrest France
Rescheduled for 3/5 per discussion.
INSP-Final Inspection2/23/20092/25/20092/25/2009ACANC
DetailsTroy Cobbley
To be rescheduled per earl Phone #: ###-####
INSP-Final Inspection11/4/200811/5/200811/5/2008PFAIL
DetailsForrest France
Noted two non-functional notification devices-locations marked on plans, hall 417 is missing adequate coverage, wall mounted a/v's at all perimeter open office locations are mounted below min. height AFF per NFPA 72, added area SD at the common corridors to be indicated on resubmitted plans. See also review note comments 10 and 11.
FIR-Aging Inspection10/31/200810/31/200811/3/2008 DONE
DetailsForrest France
Pending site inspection request for work completed.