Permit Information
Permit NumberFIR08-00480
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2308 E SOLITUDE CT
Project Name 
Customer Number 
ePlanReview 
Description
Revised FIR Sprinkler Scope: Add sprinkler coverage in the pantry, storage area, and a closet. In addition, heads in the dining room area were also relocated during construction to meet coordination requirements. There were also some minor changes of the piping in the Studio. These modifications do not appear to have an adverse affect on the remote area of operation as it was originally approved. This revision was noted on the plans and dated 08/12/08. FIR Sprinkler Scope: Install a new 13D modified fire sprinkler system through out the single story single family dwelling with a finished basement to a single row of dry sidewall sprinklers along the wall common to attached garages and the living space. System shall be equipped with an alarm initiating device and an outside alarm. The system will be supplied from an existing 2” poly dedicated fire line. (by others) All fire sprinkler work and related, which includes a single dedicated service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to BLD08-00432.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/30/20093/30/20093/30/2009APASS
DetailsForrest France
Items on correction notice have been completed, final fire sprinkler inspection passed.
INSP-Conference3/27/20093/27/20093/27/2009PDONE
DetailsForrest France
Regarding unfinished basement area ceilings.
INSP-Final Inspection3/25/20093/26/20093/27/2009AFAIL
DetailsForrest France
Noted two locations where sprinkler heads are blocked by adjacent light fixtures including the studio storage room 1st floor and a basement closet, missing sheetrock ceilings at basement rooms south side. Flow testing completed.
INSP-Supply line flush3/26/20093/26/20093/26/2009APART
DetailsForrest France
Supply line flush completed per activity notes 8/12.
INSP-Sprinkler Rough-in8/21/20088/22/20088/22/2008APART
DetailsForrest France
Plan resubmittals accepted regarding field modifications, tenting appears acceptable, noted corrections verified, overhead install is okay for cover.
INSP-Sprinkler Rough-in/Hydro8/11/20088/12/20088/12/2008AFAIL
DetailsForrest France
Overhead rough-in is not approved for cover at this time due to field changes in pipe routing/sizes, 6 added heads, one deleted head, an added kitchen storage room in an upper level including 2 heads not shown on drawings, relocated heads etc. Plans will need to be resubmitted for approval matching the field installation prior to okay for cover. Noted possible obstructions by soffits at three rooms in the basement which need to comply with NFPA 13D 8.2.5.4.3, head at the riser room needs relocated as discussed for exposed CPVC riser install, be aware of possible light fixture obstructions. UG supply flush completed okay.