INSP-Final Inspection | 8/25/2008 | 8/25/2008 | 8/25/2008 | P | PASS |
Forrest France
|
|
|
Corrections verified for compliance, fire sprinkler permit okay for final as uprights at the plan mod. area are installed.
|
INSP-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | FAIL |
Forrest France
|
|
|
The four additional heads added per plan modification are not installed-need to provide drop ceiling and pendents per plan or upright sprinklers to maintain coverage throughout.
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2008 | 8/5/2008 | 8/5/2008 | P | PART |
Forrest France
|
|
|
OH fire sprinkler modifications per the original scope of work are acceptable for ceiling cover.
|