Permit Number | FIR08-00505 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
350 N MILWAUKEE ST Unit: 2060
|
Project Name | SPR-Forever 21 Demo |
Customer Number | |
ePlanReview | |
Description |
FIR OH Work Scope:
The Fire Sprinkler scope consists of adding and relocating 172 new quick response heads to accommodate a new wall and ceiling layout in the in the Forever 21 tenant space # 2060. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-01055
To modify, as required, existing overhead sprinkler system drops to prevent damage during tenant improvements. Fire sprinkler protection shall be maintained in existing spaces during TI construction. Final head layout will be submitted under seperate fire sprinkler permit after demo phase is complete. When fire protection systems are to be temporarily put out of service, all possible work shall be accomplished in advance prior to shutting off the water to the fire sprinkler system, so that final connections can be made quickly and protection restored promptly. The chief (Fire Department) shall be notified when any required fire-protection system is out of service for over an 8-hour period and upon restoration of service.
|