Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR08-00516
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 3236 E AMITY RD
Project NameOverhead
Customer Number 
ePlanReview 
Description
FIR Work Scope:
Beginning from an existing 8” supply located in the riser room at the SE corner of the Bldg., install a 4” wet riser to serve through out the structure. A future paint Booth will be submitted under a separate permit application. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00395 & BLD08-00609 & FIR07-00905 of the UG work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/8/200810/8/200810/8/2008PPASS
DetailsTroy Cobbley
Corrections made per Forrest last inspection and forward flush completed. KR.
INSP-Final Inspection10/3/200810/6/200810/6/2008ACANC
DetailsForrest France
Bruce Phone #: ###-####
INSP-Sprinkler Rough-in9/23/20089/24/20089/24/2008APART
DetailsForrest France
Verified correction notice items are complete per last inspection, pendent heads at the paint mixing room are the correct type however plan legend indicates 286 deg. heads and 155 deg. heads have been installed. Also need to adjust deck insulation blocking one upright head prior to final. Office areas are okay for cover at the drop ceilings.
INSP-Sprinkler Rough-in/Hydro9/22/20089/22/20089/22/2008PFAIL
DetailsForrest France
OH rough-in failed due to missing SW head at an overhead door, blocked upright by deck insulation, incorrect head types at the paint storage and mixing room, overspaced pendent at the dry goods storage room, need to install flex couplings at the riser per key note #16 on plans. See annotations on stamped plan set.
INSP-Sprinkler Rough-in/Hydro9/16/20089/17/20089/17/2008APART
DetailsForrest France
Overhead hydrostatic testing passed inspection, noted FDC is obstructed as installed by adjacent bollard at the garage door entrance. Need approved plans for rough-in inspection.
INSP-Sprinkler Rough-in/Hydro9/5/20089/8/20089/5/2008PCANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick