Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR08-00520
StatusFinaled
Name MOUNTAIN ALARM
Site Address 10500 W OVERLAND RD
Project NameALBERTSONS - FIVE MILE PLAZA
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add/relocate notification devices to bring the building up to current code requirements in response to a store remodel. All initiating devices are existing and are not being touched under this permit scope.
Associated building permit: BLD08-00103 (ALBERTSONS STORE #0160)(FIVE MILE PLAZA) A phased remodel to an existing 51,100 sq. ft. grocery store building located at the west end of an existing shopping center per approved plans. Work to include some interior demolition work, some new interior walls and doors, updating some product fixtures/equipment, new suspended aisle markers, [concrete slab work over new trenches for plumbing, electrical, or refrigeration,] new interior finish and decor elements, some new suspended ceiling work, some new suspended walls/soffits, exterior site work, patch and repair existing asphalt, new exterior paint, minor fire sprinkler and alarm work, mechanical work, plumbing work, and electrical work. NOTE: This building was constructed in Ada County in 1978 and annexed into Boise City on 12/30/99. NOTE: This building is fully fire sprinklered for area increase. A letter of completion is required to final this permit. Reference MIS08-00027 for completion of upgrade agreement bld04-02214**TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/8/20091/9/20091/9/2009APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/7/20091/8/20091/8/2009AFAIL
DetailsTroy Cobbley
Lower the 110 cd strobe in the storage area, install the existing smoke detector that is over the facp to the deck, provide the missing strobe in the east storage area and retest all of the audio/visual devices.
INSP-Final Inspection1/6/20091/7/20091/7/2009ACANC
DetailsTroy Cobbley
The hood suppression system has not been tied into the fire alarm system so no inspection was performed.
INSP-Final Inspection7/31/20088/1/20088/1/2008ACANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
INSP-Final Inspection7/30/20087/31/20087/31/2008PCANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
INSP-Final Inspection7/29/20087/30/20087/30/2008PCANC
DetailsTroy Cobbley
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner