Permit Information
Permit NumberFIR08-00551
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10681 W MCMILLAN RD
Project NameSpring Creek Boise Senior Livi
Customer Number 
ePlanReview 
Description
10/11/08 Revised FIR OH Scope:
The contractor has submitted an additional remote area calculation of the attic BB1 heads upon the request of the plan reviewer. The request was based on the changes to the dry pipe systems during construction. The contractor has also submitted a corrected version of the Head Legend for review. The revisions were noted on the plans as Rev 4 and dated 10/07/08.
10/06/08 Revised FIR OH Scope:
The contractor made changes to the original design during construction. As a result of these changes to the wet & dry pipe systems, a complete new plan and supporting hydraulic calculation summary analysis was required. The revisions were noted on the plans as Rev 3 and dated 09/25/08. 09/17/08 Revised FIR OH Scope: The contractor made modifications to the original design based on plan review comments. The modifications included adding heads in the bedrooms where over-spacing accrued. The plans were also modified to include a separate remote area calculation for the Kitchen Area. Eight additional heads were added as a result of the modifications noted on the plans as Revision #2, dated 09/05/08.
Conditions of Approval: Plan FP3. The head temperature rate in the Kitchen area is noted to be 155 degree. The appliances in the kitchen area are not noted on the plans. Spacing and temperature requirements are to be field verified and changed are to be made if necessary. .NFPA13 8.3.2
Note: The hydraulic placard for remote area 8 on sheet FP3 is incorrectly notated and does not correlate with the calculations submitted. However, the calculations do appear to be correct. Please make the necessary revisions on the as-built drawing and all other copies. In the future, please submit a required Hydraulic Cover Sheet for each are submitting.
08/19/08 Revised FIR OH Scope: The contractor made changes to the original design based on changes made in the field during construction. As a result of these changes to the wet & dry pipe systems, a complete new plan and supporting hydraulic calculation summary analysis is required. The revisions were not noted on the plans.
08/05/08 FIR OH Scope: Beginning from a 6” supply located with the 1 hour rated riser room located at the NE corner of the building, install a 4” vertical wet riser and a wet pipe system to serve through out the heated areas. A dry pipe system will serve the attic and canopy areas. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00698 & UG permit FIR08-00293.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/20/200811/21/200811/21/2008APASS
DetailsTroy Cobbley
Foward flush completed, alarm inter- connection testing completed. KR
INSP-Sprinkler Rough-in11/6/200811/7/200811/7/2008APASS
DetailsTroy Cobbley
the 24 hr air test passed
INSP-Sprinkler Rough-in11/6/200811/6/200811/7/2008PPASS
DetailsTroy Cobbley
The 24 hr air test was started with 41 1/14 psi on the guage.
INSP-Sprinkler Rough-in/Hydro10/16/200810/17/200810/17/2008APASS
DetailsTroy Cobbley
The overhead hydro tests for both the wet and the dry systems passed.
INSP-Supply line flush10/16/200810/17/200810/17/2008APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in10/2/200810/3/200810/3/2008APASS
DetailsTroy Cobbley
The remaining sprinkler piping is ok to cover where the sprinkler coverage was inadequate due to the roof transitions. I kept one copy of the as-builts to be compared with the city approved plans when received.
INSP-Sprinkler Rough-in9/30/20089/30/20089/30/2008PNR
DetailsTroy Cobbley
I stopped at the job site and spoke to Ryan. This inspection was for a cover of the remaining piping. I did not give approval since the dry system piping iinstallation has been modified to provide correct protection at the roof elevation transitions; no plans for the modification were on site. This redesign effects the hydraulic calculations, siesmic calculations, volume of the dry system which could effect air compressor sizing and trip times. Approved resubmittals are required prior to cover or the contractor needs to meet with the Boise City Fire Dept. to make other arrangements for cover.
INSP-Sprinkler Rough-in9/24/20089/25/20089/25/2008APART
DetailsTroy Cobbley
All of the outstanding rough-in issues have been taken care of except for verification from Tyco that the BB1 head installation still meets the manufacturers listing at the two areas of roof transitions. I have approved cover for all areas except for these two locations. Forrest France first addressed this issue on 9-22-2008. I let Ryan know that approved resubmittals will be required prior to a final inspection. My "redlined" city approved drawings are to be submitted to Bryan Johnson with this resubmittal. The building owner was witness to and part of the above conversations. I also found one pendant head in the west wing that was overspaced. Correct spacing will be verified at the final.
INSP-Sprinkler Rough-in9/22/20089/23/20089/23/2008PFAIL
DetailsTroy Cobbley
Todays inspection was for the wet system. See the city approved plans for deficienceis and there locations. See the city approved plans for the one wing that can have the piping covered since no corrections for the wet or dry system were in this area. The rest of the building has deficiencies listed in red on the city approved plans. They include overspaced heads in the kitchen area. It appears additional heads will be required since the room size exceeds the maximum spacing of the pendant heads as calculated in the room. The size of the piping on the plans does not match what has been installed which includes the corridor remote area. Many heads are closer together than the allowed 8'-0". Heads in the corrior are blocked by a beam and will not provide coverage into the "pockets". The 2" wet system main supplied directly from the riser room has been rerouted and does not match plans. Where there were three elbows, there are now alot of tees which will add to the overall friction loss. While looking at the wet system I noticed that the side sammy's are not installed the minimum distance above the bottom of the truss as required by NFPA 13. I also verified Forrest Frances concern that the 1/4" shank side sammys are being used for piping exceeding 2 1/2" in diameter which is not allowed per the web site. The fitter did not have the specific model number of the attachment used. I let Ryan know that resubmittals will be required showing all of the changes prior to a fire sprinkler final.
INSP-Sprinkler Rough-in/Hydro9/19/20089/22/20089/23/2008ACANC
DetailsTroy Cobbley
Could this be after 9:00am. Ryan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus
INSP-Sprinkler Rough-in/Hydro9/22/20089/22/20089/22/2008PFAIL
DetailsForrest France
Dry system rough-in failed, items include two missing upright heads and piping not installed, 5 BB attic heads to be replaced due to field modified deflector orientation, overspaced coverage at one location above the riser room, noted remote inspectors test connection has been moved from where indicated on approved plan, also noted possible coverage issue at hatched areas due to change in roof pitch at zone of coverage for the BB heads. Also discovered two leaks to be repaired and bushings at some fittings.
INSP-Sprinkler Rough-in/Hydro9/22/20089/22/20089/22/2008APART
DetailsForrest France
Overhead dry system and wet system hydrostatic testing passed. KR
INSP-Sprinkler Rough-in/Hydro9/19/20089/19/20089/19/2008PCANC
DetailsTroy Cobbley
Could not make the inspection due to time constraints.
INSP-Sprinkler Rough-in/Hydro9/19/20089/22/20089/19/2008ACANC
DetailsTroy Cobbley
Ryan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus