Permit NumberFIR08-00595
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1388 S ENTERTAINMENT AVE
Project NameSpectrum Resturant
Customer Number 
ePlanReview 
Description
FIR OH Scope: 10/28/08
Corrected plans and calculations have been provided. The ECHSW heads have been changed to Pendant heads. The revision is noted as Revision #3 and dated 10/15/08.
FIR OH Scope:
Beginning from an existing 6” supply, install a 4” RPZ back flow device and wet riser to serve through out the warm areas and an auxiliary anti-freeze system to serve the cold areas. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00896 & UG permit FIR08-00514.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/9/20092/9/20092/9/2009PPASS
DetailsTroy Cobbley
permit finaled
INSP-Conference1/7/20091/7/20091/7/2009PDONE
DetailsTroy Cobbley
I spoke to Brian Johnson and to Andy, the builder, about the PIV that was shown to be installed on the overhead sprinkler plans has not been installed. Per the separate underground permit FIR08-00514 no PIV was being installed. The PIV needs to be installed, a wall PIV approved by the city of boise installed or the one hour room with exterior access provided. Brian stated that he would contact me with a solution.
INSP-Sprinkler Rough-in12/23/200812/23/200812/23/2008PFAIL
DetailsForrest France
Wrong permit number request, intended for Tenant Improvement work.
INSP-Sprinkler Rough-in11/13/200811/14/200811/14/2008APART
DetailsForrest France
Reinspection for adjusted upright head locations in the truss webs at the roof deck passed. Noted three non-sprinklered concealed spaces at the SW round- locations marked on plans- in need of coverage or meet exceptions per NFPA.
INSP-Sprinkler Rough-in11/12/200811/14/200811/13/2008ACANC
DetailsTroy Cobbley
Your contact is Richard. Thanks. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in11/4/200811/5/200811/5/2008APASS
DetailsTroy Cobbley
The east exterior canopy can be covered now that the piping type and sizing has been corrected.
INSP-Sprinkler Rough-in/Hydro10/31/200811/3/200811/3/2008APASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/29/200810/31/200810/31/2008ACANC
DetailsTroy Cobbley
Per Charles the hydro test is to be cancelled.
INSP-Sprinkler Rough-in10/30/200810/31/200810/31/2008APART
DetailsTroy Cobbley
The southwest canopy can be covered. The east canopy can not be covered due to cpvc piping being installed where as the plans indicate steel piping is to be installed. Plans either need to be resubmitted or piping is to be installed as per the plans. Also the upright sprinkler heads through out the rest of the building have not been installed as per NFPA 13 8.6.5.2.1.6 and exhibit 8.20. The general contractor also stated that he would install insulation in the eaves of the tower located on the southwest corner of the building. This space is considered a combustible concealed space.
INSP-Sprinkler Rough-in10/29/200810/30/200810/30/2008PNR
DetailsForrest France