Permit Information
Permit NumberFIR08-00601
StatusFinaled
Name ALARM STAR
Site Address 10681 W MCMILLAN RD
Project NameSpring Creek Boise Senior Livi
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new automatic and manual detection system in a new assisted living building. This system shall provide full area smoke detection, full notification, and sprinkler system monitoring. No duct detectors were shown as needed and are not part of this permit scope.

Associated building permit: BLD08-00698 ("SPRING CREEK BOISE" Senior Assisted Living) -This building is fully sprinklered for allowable area increase and occupancy use group. To construct a 16,311 sq. ft., Type VA construction, one story Assisted residential living facility building with 29 sleeping units with common associated use dining, kitchen, living room, salon, mechanical & accessible common use restroom / powder room support areas; construct a 1-hour fire-resistive rated exit corridor to serve all areas of the building, with fire rated protection of penetrations and self-closing, "S" label smoke/fire doors for opening protection; electrical, mechanical, plumbing, sprinkler and alarm installation; a minimum of 2 fully Accessible Units and all others complying as Type 'B' accessible units or better. All per approved plans to include red-line notes and all attached plan reviews of all reviewing agencies. DRH07-00476 CUP07-00175 drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/1/200812/1/200812/1/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/24/200811/25/200811/25/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/21/200811/24/200811/24/2008PFAIL
DetailsTroy Cobbley
The smoke detectors have been relocated but I found that the signals are not going out to the monitoring station. The testing of all devices will need to be redone
INSP-Final Inspection11/20/200811/21/200811/21/2008AFAIL
DetailsTroy Cobbley
Smoke detectors located in all two bedroom units are located less than three feet from bathroom door containing a shower, corrections will have to be made to final permit. All other testing has been completed. KR