Permit NumberFIR08-00607
StatusFinaled
Name R M E INC
Site Address 7201 W FAIRVIEW AVE
Project NameBURLINGTON COAT FACTORY
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new manual fire alarm system in an existing building. Permit includes pull stations, notification, duct detector monitoring, and sprinkler system monitoring.

Associated building permit: BLD08-01467 (BURLINGTON COAT FACTORY) Permit to remodel a 65,551 square foot tenant space and make cosmetic exterior changes per approved plans and CZC08-00104. Work to include: [Demolition of existing floor coverings, existing storefront, interior non-bearing walls,] {construction of interior non-bearing walls to create new accessible restrooms, a count room, a cash office, a managers office, a break room,} new flooring throughout, new cash wraps, new storefront system, and interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinklered for area increase any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/6/20094/6/20094/6/2009PPASS
DetailsTroy Cobbley
Permit finaled. It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
INSP-Alarm Testing4/6/20094/6/20094/6/2009APASS
DetailsTroy Cobbley
It took two visits to the job site before the inspection could be passed. At the first inspection it was found that the incorrect sample tubes for the duct smoke detectors had been installed. The correct sample tube were found, installed and verified this afternoon.
INSP-Final Inspection3/31/20094/1/20094/1/2009AFAIL
DetailsTroy Cobbley
The spacing of the strobes has been corrected but functionality was not tested. None of the duct smoke detectors tested shutdown upon detection of smoke. The correct orfices need to be installed in both of the fire sprinkler inspector test lines. The flow switch on the east system did not operate. The west sprinkler system flow switch was not tested. The outside alarm bell did not operate on the east sprinkler system. The sprinkler tamper switches did operate correctly.
INSP-Alarm Testing3/30/20093/31/20093/31/2009ACANC
DetailsTroy Cobbley
Cnceled due to time constraints
INSP-Alarm Testing3/26/20093/27/20093/27/2009AFAIL
DetailsTroy Cobbley
The only items tested today were the phone lines for supervision. They were programed for the supervision as I waited. The interconnect with the NAC panel was also tested. The Inspection did not proceed any further due to many of the strobes being overspaced. Spacing will need to be modified or additional strobes added. The phone line trouble signals did report to the monitoring station.