Permit Number | FIR08-00636 |
Status | Finaled |
Name |
COMMERCIAL FIRE PROTECTION
|
Site Address |
2051 S COLE RD
|
Project Name | COSTCO WHOLESALE |
Customer Number | |
ePlanReview | |
Description |
12/12/08 FIR OH Work Scope:
The Fire Sprinkler contractor has submitted an expectable impairment plan along with a revised design approach to include a higher design density of .45 over 2000-ft/2.
10/22/08 FIR OH Work Scope:
The Fire Sprinkler scope consists of raising 117 drops / dry pendants 4’-0” in the cooler / Freezer to meet new ceiling height. The ceiling will be raised to facilitate fork lift activity. The existing storage arrangement of 70% racking and 30% palletized Class II commodity to 17’-0” maximum storage height will remain the same.
09/18/08 FIR OH Work Scope:
The Fire Sprinkler scope consists of raising 117 drops to dry pendants 4’-0” in the cooler / Freezer to meet new ceiling height. The existing commodity / storage arrangement is to remain. The storage height is limited to 17’-0” as was originally designed. The existing dry pendants will be replaced with new quick response heads matching the existing. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-01890.
|