Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR08-00706
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 7557 W USTICK RD
Project NameWest Branch Public Library
Customer Number 
ePlanReview 
Description
11/28/08 Comments: These plans and calculations were resubmitted with revisions to the remote area 3 calculation. The revisions were dated 11/24/08. The plan revisions were noted as Revision Delta 2. No further comments.
11/12/08 Comments: These plans and calculations were resubmitted with the required corrections from the review dated 10/29/08. The plan revisions were noted as Revision Delta 1, and dated 11/05/08. No further comments.
OH Scope: Beginning from an existing 6” supply located with the 1 hour rated riser room, install a 4” wet riser and grid system to serve through out the entire 14,860 ft/2 structure. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00475 & UG permit FIR08-00504.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/9/20096/9/20096/9/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/5/20096/8/20096/8/2009ACANC
DetailsTroy Cobbley
The fire alarm system was not reading for testing.
INSP-Final Inspection6/5/20096/5/20096/5/2009PFAIL
DetailsTroy Cobbley
The interconnections with the fire alarm system could not be tested. The forward flow of the backflow preventor passed.
INSP-Sprinkler Rough-in4/10/20094/13/20094/13/2009APART
DetailsTroy Cobbley
The sprinkler piping can be covered. See the city approved plans for the locations of three items that need corrected such as a blocked head, painted head and an overspaced head. Also there is no computer record of the plans being resubmitted due to a sprinkler main being modified/relocated in a remote area and theFDCbeing relocated. See the previous inspection entry for these items.
INSP-Sprinkler Rough-in/Hydro4/8/20094/10/20094/10/2009APASS
DetailsTroy Cobbley
The overhead hydro test passed
INSP-Sprinkler Rough-in1/26/20091/26/20091/26/2009PPART
DetailsTroy Cobbley
The sprinkler rough-in is passed. Not all of the sprinkler drops have been installed. Final sprinkler spacing will need to be verified when drops, ceilings and soffits have been installed. The FDC has been relocated and a sprinkler main in a hydraulic remote area on the north side of the building has been rerouted. These changes will need to be verified by teh plan reviewer.