Description
This fire alarm permit is to provide a new manual fire alarm system in a new building. Permit scope to include pull stations, full notification, and HVAC & Sprinkler system monitoring.

Associated building permit: BLD08-01335 Chinden and Five Mile Church of Jesus Christ of Latter-Day Saints - To construct a new 16,400 square foot, one story wood framed church building and related site improvements. This building will contain a chapel, cultural hall, warming kitchen, classrooms and office areas. This building is fully fire sprinkled. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/12/20098/13/20098/13/2009PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection7/28/20097/29/20097/30/2009PFAIL
DetailsTroy Cobbley
All of the initiating devices were tested but when it came time to verify signals nothing matched including the building address. All devices will need to be retested. All of the duct smoke detectors have been deleted as well as the dry pipe valve. As-builts are required. Strobe coverage is missing in the east lobby. It was addressed on the city approved plans but was not dealt with during installation. Strobe coverage had to be increased in a meeting room.
INSP-Final Inspection7/28/20097/28/20097/28/2009PCANC
DetailsForrest France
Troy, Can we set this up for 3:00ish? Please call me as soon as you may know, so that I can set up the sprinkler guys. Thanks, Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
INSP-Final Inspection7/28/20097/29/20097/28/2009ACANC
DetailsTroy Cobbley
Troy, Can we do this early in the morning? Please let me know as soon as possible, so I can set it up with the GC and the Sprinkler guys. Thanks, Jason ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
FIR-Aging Inspection5/19/20095/19/20095/19/2009 NR
DetailsTroy Cobbley
Work is in progress.