Permit Information
Permit NumberFIR08-00750
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 650 N ARMSTRONG PL
Project NameWINCO CORPORATE OFFICE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing Simplex fire alarm system with a new Honeywell fire alarm system. Permit scope to include a full manual system, with notification, Ansul system trigger, and sprinkler system monitoring. No HVAC has been shown on the plans as being part of this permit. There is no associated building permit.

NOTE: 3/3/09 - Floorplan layout (walls) have been modified. There are a few areas (see redlines on plans) where it is not clear what is being demo'd and what is actually there. Some notification may need to be added if these areas have full height walls rather than the assumed 'cubicles'. Inspector to field verify NFPA 72 spacing requirements have been met.

NOTE: 3/24/09 - Duct detectors have been added and additional floorplan layout (walls) have been modified. Some notification may need to be added in areas that have full height walls rather than the assumed 'cubicles' (see redlines on plans). Inspector to field verify NFPA 72 spacing requirements have been met.

Associated building permit: BLD08-01127 Winco - Office Expansion and Remodel - To construct a 40,790 square foot, one story masonry and wood framed office addition on the east end of the existing Winco office building. The new addition will include an entry lobby, break room, focus assembly room, gym, locker rooms, restrooms and office areas. This permit is also for remodel work at the existing building, including converting existing 1,200 square foot entry to future work area, remodel a 912 sq. ft. office area configuration at offices #169 - #173 and offices #179 - #183 and to remodel a 1450 square foor office area configuration at offices #112 - #132. This permit also includes related site improvements. This building is fully fire sprinkled. The sprinklers are used for area increase. The assembly areas are viewed as accessory spaces to the main Office B Occupancy per IBC, Section 508.3.1. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/27/20093/30/20093/30/2009APASS
DetailsTroy Cobbley
Permit finaled. The reporting to the central station had to be changed.
INSP-Final Inspection3/27/20093/27/20093/27/2009PFAIL
DetailsTroy Cobbley
I received a phone call asking me to please perform an afternoon inspection even though it was not called in. I arrived at the project and found that the fire alarm system was still in the process of being installed. I went ahead and did a preliminary inspection and found the new manual pull stations had been installed too high and one was located too far from the exterior exit door. We set off the audio/visuals which passed sync and functionality. Several a/vs, see the as-built plans, need to be brighter or be relocated to provide code compliant coverage. See the correction notice left on site for a full list of items needing addressed.
INSP-Final Inspection1/28/20091/29/20091/29/2009APART
DetailsTroy Cobbley
The area "A" system has passed testing. Revised plans incorporating all of the changes as noted on the inspection entry dated 1-28-09 are to be resubmitted for approval prior to final inspection and signoff when area "B" is complete.
INSP-Alarm Testing1/27/20091/28/20091/28/2009PFAIL
DetailsTroy Cobbley
Bruce provided me with a set of as-built plans upon arrival. These as-built plans do not reflect the actual installation and the installation is not code compliant in several respect. A resubmittal for plan review is required, which is to include as built modifications and revised NAC circuit calculations. I annotated the corrections needed in red ink on the as builts for their reference. These corrections include strobes that are overspaced off of walls in several areas, and an area in the Mail Room that has no strobe coverage at all but is required due to a full height wall that was not shown on the plans; a strobe that was installed in the Mail Room which was not shown on the as-builts, an additional pull station which is required at the north exit door that is not installed or shown on the approved plans, the fire alarm panel which is not located as shown on the city approved plans but is now located in a room completely across the building; an additional fire sprinkler riser with a PIV tamper switch, two backflow tamper switches and a flow switch which has been connected to the new fire alarm system which was not shown on the city approved fire alarm plans. Also per the scope of work there are no hvac smoke duct detectors shown but the as-builts show two hvac units with detectors and interconnection with the FACP which matches the installation. Approved resubmittals will be required prior to final inspection of this project showing all of the listed changes and any others as the inspection progresses. The items that were tested today and passed are all of the new sprinkler devices, phone lines, NAC interconnects and the two area smoke detectors. The two duct smoke detectors were not tested due to not having access to the temperature controls for the hvac units.
Also the installation has only been done for area A as shown the issued plans; area B is to be completed after relocating the occpants into area A after it has been completed and approved for occupancy; at which time the existing Simplex will be removed and devices connected to the new FACP. This Phasing was not indicated on the Alarm Application but will be acceptable as long as alarm monitoring is not interrupted.