INSP-Final Inspection | 2/12/2009 | 2/13/2009 | 2/13/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. The recall function of the machine room smoke and heat detectors was modified while on site for correct function. The duct smoke detectors were factory installed and tested ok. A larger more legible map is to be installed at the remote annunciator.
|
INSP-Final Inspection | 2/5/2009 | 2/6/2009 | 2/6/2009 | A | FAIL |
Troy Cobbley
|
|
|
Per Scotty the project is not ready for inspection.
|
INSP-Final Inspection | 2/2/2009 | 2/3/2009 | 2/3/2009 | A | FAIL |
Troy Cobbley
|
|
|
Provide print out of todays signal report, test the duct smoke detectors, provide verification of review comment #20, provide verification of sprinkler coverage at the top of the elevator shaft, provide automatic disconnect and monitoring of the 120 volt power as per review note #6, provide firemans hat functions, recall and shunt trip functions as per 6.16.3, provide as builts showing the additional devices, relocate the smoke and heat detectors to the deck, repair the PIV tamper switch.
|