Permit NumberFIR08-00776
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 190 E BANNOCK ST
Project NameST LUKES-S EAST + E ANNEX
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add a pull station, notification, and area smoke detection coverage for f/s damper shutdown due to the outpatient area remodel.

Associated building permit: BLD07-01692 (ST LUKES - SOUTH - EAST + EAST ANNEX - PHASE V REMODEL - PACU, ANESTHESIA WORK ROOM, SAT. PHARMACY) This building is fully sprinklered based on occupancy use group. To remodel approximately 12,750 sq. ft. of existing hospital area to update and improve patient care services & for operating room prep and recovery and support services. Work includes select interior demolition; construction of non-combustible, non-rated & fire-rated, fire-resistive walls; upgrade of electrical, mechanical, plumbing, med gas, sprinkler and alarm systems; suspended ceiling grid, interior finishes and millwork, all per reviewed plans. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/10/20096/11/20096/11/2009APASS
DetailsForrest France
Remainder of fire alarm devices per the scope of work passed testing, permit finaled.
INSP-Alarm Testing5/13/20095/14/20095/14/2009APASS
DetailsTroy Cobbley
Four smoke detectors and one manual pull station were tested. They are located in phase 5, sub phase 4 and 5. See the city approved plans with todays date and my name written at each device. Items tested ok.
INSP-Alarm Testing2/26/20093/2/20093/2/2009APART
DetailsForrest France
See locations initialed on approved plan set with today's date for three in duct detectors, two area detectors and two notification devices tested, noted one HVAC grill to be relocated as discussed.
INSP-Alarm Testing1/7/20091/8/20091/8/2009APART
DetailsForrest France
See approved plan set for locations of devices inspected and passed today including dampers, strobes, smoke detectors-noted one SD at the corridor address #58 to be relocated due to proximity to an HVAC diffuser, existing MP #101 tested okay.