Permit Information
Permit NumberFIR08-00787
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3896 N WOODY LN
Project NameIntermountain Property Dev
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of installing a 13D fire protection for a Live/Work unit.

Associated building permit BLD08-00224 (live/work unit 25) To construct a 2,000 sq.ft., two story, Live/Work unit (Townhouse) on a zero lot line. The First story includes a 756 sq.ft. non-residential use, operated by the tenant and shall comply with section 419 of the 2007 International Building Code Supplement. The first story also has a 36 sq.ft. covered porch, a 89 sq.ft. covered patio, and a 464 sq.ft. attached two car garage. A maximum of five non-residential workers or employees are allowed to occupy the non-residential area at any one time. The second story includes a 1,244 sq.ft., two bedroom, two bathroom, dwelling unit with a 89 sq.ft. balcony. The dwelling unit shall comply with the 2006 International Residential Code for a Single family townhouse dwelling. This building shall conform to section 903.3.1.3 of the 2006 IBC. An automatic sprinkler system shall be installed throughout in accordance with NFPA 13D. Any and all NFPA 13D systems shall be equipped with an alarm initiating device commonly referred to as a flow switch, and an outside alarm indicating device. A Fire Sprinkler Permit is required prior to beginning any fire sprinkler work. "This lot is within a Floodplain area. An elevation certificate is required to be submitted to and approved by Jim Wyllie, Public Works Department, prior to calling for a framing inspection." All work per the approved plans, engineering, plan review report, and alternate agreements on file. DRH07-00466, DRH08-00126, and CUP07-00121 per Planning and Zoning. **SRZ**

System Design History
This is a new fire protection system design per (IRC 2007 Supplement for Live/Work Unit) that references NFPA 13d.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/27/20094/28/20094/28/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/23/20094/27/20094/27/2009PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in3/4/20093/4/20093/4/2009PPASS
DetailsTroy Cobbley
Per Tim Frost the deficiencies have been corrected and the sprinkler piping can be covered.
INSP-Sprinkler Rough-in/Hydro2/25/20092/25/20092/25/2009PFAIL
DetailsTroy Cobbley
One additional head required above the stairway for proper coverage.
1" install on the second floor when the plan indicates 1 1/4"
Main shifted approximately 5' on the second floor. Shifting the mains affected the hydraulic most remote area.
One head was leaking and was being replaced on the second floor.
Resubmittal of plans is required. Tim Frost