INSP-Final Inspection | 6/9/2009 | 6/10/2009 | 6/10/2009 | A | PASS |
Troy Cobbley
|
|
|
permit passed
|
INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 | A | CANC |
Troy Cobbley
|
|
|
Ray McQueen Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 1/29/2009 | 1/30/2009 | 1/30/2009 | A | FAIL |
Troy Cobbley
|
|
|
The city approved plans do not reflect the actual installation. Instead of one new point there are two and a supervisory signal from the vesda is connected directly to the wireless dialer which is not allowed. Provide as-builts and wire the panels correctly.
|
INSP-Final Inspection | 1/19/2009 | 1/20/2009 | 1/20/2009 | P | CANC |
Troy Cobbley
|
|
|
Ray McQueen Phone #: ###-#### Internet Inspection Request from: Diane Turner
|