Permit Information
Permit NumberFIR08-00855
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6032 N FIVE MILE RD
Project NameLDS Church
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consist of a new fire protection system for a new building, including, a wet system for the below portion and a dry system for the attic. Chinden and Five Mile Church of Jesus Christ of Latter-Day Saints - To construct a new 16,400 square foot, one story wood framed church building and related site improvements. This building will contain a chapel, cultural hall, warming kitchen, classrooms and office areas. This building is fully fire sprinkled. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20097/29/20097/30/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro5/11/20095/12/20095/12/2009PPASS
DetailsTroy Cobbley
The overhead hydro test including the fdc passed
INSP-Sprinkler Rough-in/Hydro5/5/20095/6/20095/6/2009APART
DetailsTroy Cobbley
Both of the above ground hydro tests failed. The wet system had visable leakage on the mezzanine. The FDC was not part of the hydro test and wil need to be included as per NFPA 13. The corrections noted on the previous inspection have been corrected and the remaining piping can be covered.
INSP-Sprinkler Rough-in/Hydro5/5/20095/5/20095/5/2009PCANC
DetailsTroy Cobbley
Canceled due to time constraints.
INSP-Sprinkler Rough-in4/17/20094/20/20094/20/2009PPART
DetailsTroy Cobbley
Seven upright heads need to be added as marked on the city approved plans. One piece of sprinkler piping on the plans has no designation and 4" piping has been installed where 3" is shown on the plans. Sprinkler piping can be covered except where these problems are located.
INSP-Sprinkler Rough-in2/27/20092/27/20093/2/2009PPASS
DetailsTroy Cobbley
Ok to Cover Foyers on the first floor but not outside the foyers which are protected from the above systems.
Ok to Cover Rooms 150 and 151, and bathrooms on First Floor.
INSP-Sprinkler Rough-in2/26/20092/26/20092/26/2009PCANC
DetailsTroy Cobbley
To be rescheduled per the fire sprinkler contractor.
INSP-Sprinkler Rough-in2/23/20092/23/20092/23/2009PFAIL
DetailsTroy Cobbley
Resubmittal of drawings required. Drawings do not match installation. Antifreeze system was installed instead of the dry system that was shown on the plans.