INSP-Final Inspection | 4/8/2009 | 4/9/2009 | 4/9/2009 | P | PASS |
Forrest France
|
|
|
Corrections field verified, as-builts okayed, EOL voltage drop is acceptable, fire alarm permit finaled.
|
INSP-Final Inspection | 4/7/2009 | 4/8/2009 | 4/8/2009 | A | FAIL |
Forrest France
|
|
|
Need to install a WP notification appliance as per approved plans in the beer cooler, HS at the refrigeration equipment mechanical room is obstructed, missing coverage at the deli counter food preparation room, coverage between ceiling mount 115cd strobes at the sales floor between ceiling elevation changes/obstruction to be verified during functional test.
|
INSP-Final Inspection | 4/3/2009 | 4/7/2009 | 4/7/2009 | A | CANC |
Forrest France
|
|
|
Inspection rescheduled 4/8.
|
INSP-Final Inspection | 4/2/2009 | 4/3/2009 | 4/3/2009 | A | CANC |
Troy Cobbley
|
|
|
Per mike this will be rescheduled for tuesday morning.
|