Permit Information
Permit NumberFIR09-00096
StatusFinaled
Name BIG M ELECTRIC INC
Site Address 4906 N CLOVERDALE RD
Project NameBoise Retirement Residence
Customer Number 
ePlanReview 
Description
BLDG B PLAN MODIFICATION 10-19-09:
This plan modification includes providing modules for synchronizing the audibility between the room notification devices and the building notification devices. This modification also includes implementing as-built devices and previous plan review comments.

This fire alarm permit is to provide a new fire alarm system in a new building. Permit scope includes automatic smoke detection system with full notification, monitoring for HVAC, dampers, and sprinkler system, Elevator recall functions, smoke shutters in the 3rd floor atrium, fire doors, a fire pump, kitchen hood suppression system monitoring, and an emergency generator.

Associated building permit: BLD08-02085 (BOISE RETIREMENT RESIDENCE - BLDG B - EAST SECTION) To construct a new 60 unit 44,546 square foot, three story, I-1, non state licensed, residential care assisted, living facility, where all residence will be capable of responding to an emergency situation without physical assistance. This building to be fully fire sprinklered with an NFPA 13 system for area increase. This area is separated from the center building (Section A) by a 2-hr. fire wall. Note: This project was reviewed by ICC for energy, structural, nonstructural and accessibility requirements for code compliance. (52 units less than 800 sq.ft. and 8 units more than 800 sq.ft.)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/20/200910/20/200910/20/2009PPASS
DetailsTroy Cobbley
The syncing of the handicap rooms a/v's has been addressed. The placement and testing of the atrium smoke detectors has been addressed. Permit finaled.
INSP-Alarm Testing4/9/20094/9/20094/9/2009PPASS
DetailsTroy Cobbley
This inspection was a fire alarm rough-in on the first and second floors which passed. The horns on all floors of this building have been relocated to meet the requirements of NFPA 72.
INSP-Alarm Testing4/3/20094/6/20094/6/2009APART
DetailsTroy Cobbley
Todays inspection was for the fire alarm rough-in for the 3rd floor of building "B". The rough-in in general passed except that the horns in the rooms are not mounted at the correct heights as per NFPA 72 - 7.4. Per a conversation with Mike the strobes will be relocated to meet code requirements. Also no fixtures have been installed which may cause obstruction problems.
INSP-Alarm Testing4/2/20094/3/20094/3/2009AFAIL
DetailsTroy Cobbley
Approved drawings could not be found when I arrived at the job site. Will be rescheduled for monday.