Permit NumberFIR09-00097
StatusFinaled
Name BIG M ELECTRIC INC
Site Address 4890 N CLOVERDALE RD
Project NameBoise Retirement Residence-A
Customer Number 
ePlanReview 
Description
BLDG A PLAN MODIFICATION 10-19-09:
This plan modification is to provide information on the atrium shutters, includes providing modules for synchronizing the audibility between the room notification devices and the building notification devices, as well as to implement as-built devices and previous plan review comments.

10/6/09 PLAN MODIFICATION: This plan modification is intended to include information on the atrium shutters as well as as-built information.
FAIL: Not all as-built information has been incorporated into the plans. Contractor (Mike Pemberton of Big M Electric) has been notified via telephone that a resubmittal is required to incorporate additional smoke detectors in the atrium planters as well as implementing all changes due to job site revisions as well as previous review comments.

This fire alarm permit is to provide a new fire alarm system in a new building. Permit scope includes automatic smoke detection system with full notification, monitoring for HVAC, dampers, and sprinkler system, Elevator recall functions, smoke shutters in the 3rd floor atrium, fire doors, a fire pump, kitchen hood suppression system monitoring, and an emergency generator.

Associated building permit: BLD08-02083 (BOISE RETIREMENT RESIDENCE - BLDG A - CENTER SECTION) To construct a new 26 unit (plus manager & co-manager units) 37,512 square foot, three story, I-1, non state licensed, residential care, assisted living assisted living facility, where all residence will be capable of responding to an emergency situation without physical assistance. This building will contain the supporting occupancies such as assembly areas, dining area, associated kitchen, and an atrium all per approved plans. This building to be fully fire sprinklered with an NPFA 13 system for area increase and the atrium area. This building section is separated from the west end (Section C) and the east end (Section B) by 2-hr. fire walls. Note: This project was reviewed by ICC for energy, structural, nonstructural and accessibility requirements for code compliance. (25 units are less than 800 sq.ft. and 3 units are more than 800 sq.ft.)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/20/200910/20/200910/20/2009PPASS
DetailsTroy Cobbley
The syncing of the handicap rooms a/v's has been addressed. The placement and testing of the atrium smoke detectors has been addressed. Permit finaled.
INSP-Alarm Testing10/9/200910/9/200910/9/2009APASS
DetailsTroy Cobbley
The sync issue between the common area a/v's and the handi-cap room a/v's has been resolved and tested ok. Waiting on the resubmittals showing this work and the resolution with the atrium.
INSP-Alarm Testing10/1/200910/1/200910/1/2009PPASS
DetailsTroy Cobbley
All of the smoke alarms were tested today as well as all of the fire sprinkler to fire alarm panel interconnections. There are two items left that need addressed. They are the shutters on the third floor atrium and the non-syncing of the horn/strobes in the first floor common areas and the handi-cap rooms.
INSP-Final Inspection9/29/20099/30/20099/30/2009AFAIL
DetailsTroy Cobbley
The smoke duct detectors for hvac shutdown and the fire/smoke dampers passed inspection today. Also the hood suppression system interconnection passed inspection. The 14ga wire has been installed at the NAC panels as well.
INSP-Final Inspection9/28/20099/29/20099/29/2009AFAIL
DetailsTroy Cobbley
The inspection continued today. Items left to test include the hood suppression system, hvac shutdown, EOL voltage drop, smoke alarms, smoke shutters/atrium smoke detectors and sprinkler system interconnections. Notification and initiating (smoke detectors/pull stations) were tested on all floors. Two were repaired while I waited.
INSP-Final Inspection9/25/20099/28/20099/28/2009AFAIL
DetailsTroy Cobbley
See the city approved plans for the initiating devices tested today as marked in red. The phone lines and supervision of the NAC panels were verified. One 16ga wire needs to be changed to 14ga as discussed and atrium smoke shutter sequence of operation needs to be verified since it has not been programmed per the approved drawings.
INSP-Alarm Testing7/6/20097/7/20097/7/2009APASS
DetailsTroy Cobbley
The rough-in inspection for the riser room is passed.
INSP-Alarm Testing7/1/20097/1/20097/1/2009PPASS
DetailsTroy Cobbley
The fire alarm rough-in for the first floor passed.
INSP-Alarm Testing6/24/20096/24/20096/24/2009PPASS
DetailsTroy Cobbley
The fire alarm rough-in for the second floor passed. One smoke detector appears to be overspaced from the east fire doors and will be verified at the final.
INSP-Alarm Testing6/9/20096/9/20096/10/2009PDONE
DetailsTroy Cobbley
This was a rough-in inspection for the center building third floor fire alarm system which passed.
INSP-Alarm Testing4/8/20094/8/20094/9/2009PCANC
DetailsTroy Cobbley
The wrong inspection number was called in.
INSP-Sprinkler Rough-in4/6/20094/6/20094/7/2009PCANC
DetailsTroy Cobbley
wrong permit called in.