ePlanReview 
Description
6/5/09 PLAN MODIFICATION
This plan modification is to add voluntary notification devices to the existing fire alarm system. Notification is not required in this building; however the owner has requested it.
NOTE TO INSPECTOR: The notification requirements of NFPA 72 shall ONLY apply to the scope of the plan modification dated 6/5/09, and not to the notification devices installed for the releasing system.
___________________________________________________________________________________

3-11-09
This fire alarm permit is to replace an existing FACP sprinkler monitoring panel with new and installing a new clean agent suppression system with notification in selected areas. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/200911/25/200911/25/2009PPASS
DetailsTroy Cobbley
Permit finaled. The releasing system devices were spot checked for functionality.
INSP-Final Inspection10/5/200910/7/200910/7/2009AFAIL
DetailsTroy Cobbley
The module monitoring trouble on the NAC panel has been provided and tested. The 18ah batteries are now added and both sets of approved plans are on site. The EOL voltage is passed on the circuit over the office area of the building. The inspection was stopped from sending additional signals due to the AES panel being at a Netcom 6. It temporarily went to a Netcom 5 but then went back to a 6. Also the sound from the horns on the notification circuit is not sync'd as required per NFPA 72 Chapter 6. Placement of the notification devices appeared to be ok except back in a storage room where the strobe was not placed as per the plan and now coverage is lacking. This device will need to be relocated or an additional device added.
INSP-Final Inspection9/24/20099/25/20099/25/2009ACANC
DetailsTroy Cobbley
Overbooked. Contacted David .
INSP-Final Inspection9/16/20099/21/20099/21/2009AFAIL
DetailsTroy Cobbley
No real inspection was started. The most up to date plans showing the plan modification/audio visuals was not on site. The batteries in the FACP are incorrect. Dave was going to cordinate with Treasure Valley Fire to test the alarm valve interconnection. The trouble monitor module located at the remote power supply has not been installed. No other items have been tested or inspected.
FIR-Aging Inspection6/12/20096/12/20096/12/2009 NR
DetailsTroy Cobbley
Work in progress