INSP-Final Inspection | 11/24/2009 | 11/25/2009 | 11/25/2009 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. The releasing system devices were spot checked for functionality.
|
INSP-Final Inspection | 10/5/2009 | 10/7/2009 | 10/7/2009 | A | FAIL |
Troy Cobbley
|
|
|
The module monitoring trouble on the NAC panel has been provided and tested. The 18ah batteries are now added and both sets of approved plans are on site. The EOL voltage is passed on the circuit over the office area of the building. The inspection was stopped from sending additional signals due to the AES panel being at a Netcom 6. It temporarily went to a Netcom 5 but then went back to a 6. Also the sound from the horns on the notification circuit is not sync'd as required per NFPA 72 Chapter 6. Placement of the notification devices appeared to be ok except back in a storage room where the strobe was not placed as per the plan and now coverage is lacking. This device will need to be relocated or an additional device added.
|
INSP-Final Inspection | 9/24/2009 | 9/25/2009 | 9/25/2009 | A | CANC |
Troy Cobbley
|
|
|
Overbooked. Contacted David .
|
INSP-Final Inspection | 9/16/2009 | 9/21/2009 | 9/21/2009 | A | FAIL |
Troy Cobbley
|
|
|
No real inspection was started. The most up to date plans showing the plan modification/audio visuals was not on site. The batteries in the FACP are incorrect. Dave was going to cordinate with Treasure Valley Fire to test the alarm valve interconnection. The trouble monitor module located at the remote power supply has not been installed. No other items have been tested or inspected.
|
FIR-Aging Inspection | 6/12/2009 | 6/12/2009 | 6/12/2009 | | NR |
Troy Cobbley
|
|
|
Work in progress
|