INSP-Final Inspection | 10/1/2009 | 10/2/2009 | 10/2/2009 | A | PASS |
Forrest France
|
|
|
Final walkthrough, noted correction items, and trip testing for the two new dry systems completed satisfactory. Fire sprinkler permit okayed for final.
|
INSP-Final Inspection | 9/30/2009 | 10/1/2009 | 10/1/2009 | A | DEFR |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 9/30/2009 at 10:55:01 AM. Contact: ###-####.
|
INSP-Final Inspection | 9/28/2009 | 9/28/2009 | 9/28/2009 | P | PART |
Forrest France
|
|
|
|
INSP-Final Inspection | 9/23/2009 | 9/24/2009 | 9/24/2009 | P | NR |
Forrest France
|
|
|
|
INSP-Alarm Testing | 8/27/2009 | 8/28/2009 | 8/28/2009 | A | PART |
Forrest France
|
|
|
Pneumatic testing for the new dry system concluded per inspection by T. Frost.
|
INSP-Alarm Testing | 8/27/2009 | 8/27/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
Fire alarm testing is not ready at this time, contractor requested inspection type be changed to begin 24 hr. air test of the new dry sprinkler system- Test started at 3:00pm @ 43psig 8/27/09 by T. Frost.
|
INSP-Sprinkler Rough-in/Hydro | 8/26/2009 | 8/27/2009 | 8/27/2009 | A | PART |
Forrest France
|
|
|
Hydrostatic testing completed satisfactory for the new attic and second floor dry system.
|
INSP-Sprinkler Rough-in/Hydro | 8/25/2009 | 8/26/2009 | 8/26/2009 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to time constraints. No inspection was performed.
|
INSP-Sprinkler Rough-in/Hydro | 8/25/2009 | 8/25/2009 | 8/25/2009 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping in the interstitial space and the attic area passed inspection. Steve and I noted several chase doors that will need to be removed/permanantly closed that are obstructing attic sprinklers. Several shipping caps had been left on the uprights and steve will go through the system and re-verify that all have been removed. Viking was in the process of lenghtening several sprig ups and providing additional hangers at arm-overs in the interstitial space.
|
INSP-Sprinkler Rough-in/Hydro | 8/19/2009 | 8/20/2009 | 8/21/2009 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test for the new dry system above the band room passed, noted air compressor serving this system to be hard wired, upright at the valve room is obstructed.
|
INSP-Sprinkler Rough-in/Hydro | 8/14/2009 | 8/17/2009 | 8/18/2009 | A | PART |
Forrest France
|
|
|
Overhead work sheet FP 5 north half classroom wing inspected today including the dry system above the band room. See notations on plan for correction items at classroom 214 for a branch line to be regraded, two obstructed pendent heads at classroom 211, noted choir room 219 inspectors test has been relocated-field mod. okayed, main tie-ins at 5 locations in the corridor are not finished, missing coverage at the new dry valve riser enclosure in the band room-sheet FP3. Attic area not yet inspected.
|
INSP-Sprinkler Rough-in/Hydro | 8/11/2009 | 8/12/2009 | 8/12/2009 | A | PART |
Forrest France
|
|
|
Inspection for the second floor classrooms sheet FP4 completed today excluding the corridor not yet finished. Noted items include missing flexible couplings at four locations, one open outlet at the library room for attic protection, missing return bend per detail #7 on plans at four pendent heads, main and branch line pitch for dry systems to be maintained per NFPA, annotated field changes at two rooms for sw heads installed in lieu of pendent heads as shown on plans.
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2009 | 8/10/2009 | 8/10/2009 | P | PART |
Forrest France
|
|
|
Rough-in for overhead work at the new gym and stage areas per red-lines on plan set okayed with the exception of two overspaced locations below duct shafts at the stage stair landings, chair/table storage below the stage must be non-combustible or provide sprinkler protection, noted minor changes at branchline feeds for tailbacks at the east side of the gym. Hydrostatic testing for the gym system passed.
|
INSP-Conference | 7/29/2009 | 7/29/2009 | 7/29/2009 | P | DONE |
Forrest France
|
|
|
On site meeting with CM company, United Water, and Boise School district regarding backflow prevention device locations at the main fire riser.
|
INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/22/2009 | 7/22/2009 | A | PART |
Forrest France
|
|
|
Overhead rough-in for the first floor classroom wing sheet FP-2 okayed as red lined with today's date. Sizing changes at the main to match with approved plan set.
|
INSP-Sprinkler Rough-in/Hydro | 7/10/2009 | 7/10/2009 | 7/10/2009 | P | PART |
Forrest France
|
|
|
Okay to cover ceilings at the north classroom wing per notations on plan, also inspected rough-in above the folding partition wall at the new gym.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2009 | 7/9/2009 | 7/10/2009 | A | PART |
Forrest France
|
|
|
See red-line annotations on plan set for classroom wing first floor north side inspected today. Noted two overspaced heads at the office area, rough-in at one classroom does not match approved design, bandroom is incomplete as upright protection above the ceiling remains to be added. Hydrostatic test for the 1st floor classroom wet system passed.
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2009 | 6/17/2009 | 6/18/2009 | P | PART |
Forrest France
|
|
|
Basement area rough-in okayed per red-line annotations.
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2009 | 5/22/2009 | 5/22/2009 | A | PART |
Forrest France
|
|
|
See stamped plan set for overhead rough-in inspected to date.
|
INSP-Sprinkler Rough-in/Hydro | 5/19/2009 | 5/20/2009 | 5/21/2009 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for the new system piping at the basement level as annotated on plan sheet FP1 completed satisfactory. OH rough-in also done for this area in conjunction with the hydrostatic test-noted blocked uprights at a storage room, final head locations may need adjusted as ceilings and lights are installed.
|