Permit NumberFIR09-00182
StatusFinaled
Name ALARMCO
Site Address 833 W DIAMOND ST
Project NameECCO ELECTRONICS
Customer Number 
ePlanReview 
Description
4-22-09 PLAN MODIFICATION:
Contractor resubmitted for a plan modification to include monitoring alarm, trouble, and supervisory functions on an existing preaction system.

This fire alarm permit is to replace the existing fire alarm system with new. Permit scope includes the addition of notification where required, duct detectors, elevator recall, pull stations, and sprinkler system monitoring. An early start agreement applies to this project.

Associated building permit: BLD08-02383 (ECCO) Remodel to a portion of the existing 40,335 square foot first floor and a first time tenant improvement to the 9,230 square foot second floor. NOTE: This building is fully fire sprinklered for area increase. Work to the first floor to include: Adding new elevator, elevator equipment room constructed of 8" concrete smooth surface block on the exterior of the building, new Concore 2500 Access floor panel system in the server room, extending the existing server room walls to the underside of the second floor, construction of new walls for a lab area with a new door/tempered window, construction of new walls for a break room, and other misc. work per the plans. Work to the second floor to include: Construction of new walls for a new conference room, offices, mail room, smaller conference room, corridor with a breakroom/coffee station, one men's restroom, one women's restroom, one unisex restroom, and second floor framing construction for new HVAC and janitor/storage rooms. Second floor misc. work to include: New glass handrail, relocating a ducting chase, modifying the vestibule ceiling, sloping gypcrete flooring down to plywood floor landings at both stairs, and adding office cubicles. All work per approved plans, Engineering, attached Plan review report, and CZC08-00167. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/15/20095/15/20095/15/2009PPASS
DetailsForrest France
Remaining two correction notice items completed, contractor to provide signals list and offsite account information for verification as discussed to PDS fire office.
INSP-Alarm Testing5/13/20095/14/20095/14/2009AFAIL
DetailsForrest France
Duct detector at the conference room 2nd floor needs to shut down power to the HVAC unit immediately upon smoke detection, missing mag lock interconnection relay to drop power to the door locks upon fire alarm activation.
INSP-Final Inspection5/12/20095/13/20095/13/2009AFAIL
DetailsForrest France
Duct detector at the conference room failed to shut down power to the HVAC unit, DD at the mechanical room programed incorrectly, horns and strobes are not in sync. on the 1st or 2nd floors, fire hat at the elevator is not repaired, reinspection fees will apply.
INSP-Final Inspection5/5/20095/6/20095/6/2009AFAIL
DetailsForrest France
All three duct detectors failed to shut down HVAC units, notification devices at the second floor are not in sync, elevator hat does not flash upon machine room initiating device activation, voltage monitor for shunt trip is not provided for at the FACP, missing notification at one conference room on the 1st floor, overspacing at the elevator lobby and breakroom, notification at the 1st floor not tested due to adjustments to be made.