INSP-Final Inspection | 11/18/2009 | 11/18/2009 | 11/18/2009 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit okayed for final status, corrections completed.
|
INSP-Final Inspection | 9/15/2009 | 9/16/2009 | 9/17/2009 | A | PART |
Forrest France
|
|
|
TOC approved.
|
INSP-Sprinkler Rough-in/Hydro | 9/8/2009 | 9/8/2009 | 9/8/2009 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic testing passed, final pending project related fire alarm permit work, main drain valve does not need to be electricaly supervised, need "911" sign at the outside bell.
|
INSP-Sprinkler Rough-in/Hydro | 9/4/2009 | 9/4/2009 | 9/8/2009 | P | PART |
Forrest France
|
|
|
John Phone #: ###-####
|
INSP-Sprinkler Rough-in | 8/26/2009 | 8/26/2009 | 8/28/2009 | P | PART |
Forrest France
|
|
|
See inspection comments per site visit by T. Frost dated 8/26-Missing SW sprinklers below the garage doors if they are going to be roll back doors. Riser is not stacked. Roof top heater is blocking sprinkler discharge. Ceiling areas are OK to cover.
|
INSP-Sprinkler Rough-in | 7/29/2009 | 7/29/2009 | 7/29/2009 | P | PART |
Forrest France
|
|
|
Okay to cover hard lid ceilings at the mens and womens restrooms per red lines and initials on stamped plan set.
|