Permit NumberFIR09-00321
StatusFinaled
Name MOUNTAIN ALARM
Site Address 9600 W BETHEL CT
Project NameWILSON BUILDING
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing Radionics FACP with new and to provide an AES Radio transceiver rather than a DACT. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20111/5/20111/6/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/28/201012/28/201012/28/2010PCANC
DetailsTroy Cobbley
To be rescheduled with the two AES permits on Phillippi
FIR-Aging Inspection12/8/201012/8/201012/16/2010 NR
DetailsTroy Cobbley
Per Brett he is waiting on a points map for the facp and then will call in the inspection.
INSP-Final Inspection3/16/20103/16/20103/16/2010PFAIL
DetailsTroy Cobbley
The dedicated circuit has been provided but the map and NFPA 72 forms are still needed.
INSP-Final Inspection10/28/200910/30/200910/30/2009AFAIL
DetailsTroy Cobbley
Provide dedicated circuit as per the review comments and NFPA 72 and provide a map at the facp as discussed.
INSP-Final Inspection9/23/20099/24/20099/24/2009PCANC
DetailsTroy Cobbley
No actual inspection was performed. I spoke to Tim on the phone and we discussed the IFC 903.4 requirement for the sprinkler control valves to be supervised by the fire alarm panel. The inspection is to be rescheduled.