Permit Information
Permit NumberFIR09-00364
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 5521 E WARM SPRINGS AVE
Project NameRiverstone International Lower
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of one new wet pipe system to protect a new school. The building has composite wood joist. There are sprinklers above and below the ceiling. There is to be no unprotected combustible concealed space therefore a minimum hydraulic most remote area of 3000 sf is not required. The classroom wings do not have a ceiling and are constructed of steel bar joist with wood top and bottom chords. Piping 1 ΒΌ" and larger to be DynaFlow or Sch 10, 1" to be SCH 40.

Riverstone International Lower School - ESC08-01050 under the grading permit--To construct a new 24,300 square foot, one story elementary school building. This building will be constructed of concrete tilt-up exterior walls and wood framed construction. This permit will also include related site improvements. All construction per the approved plans and attached comment list. DRH08-00393 - JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/28/200912/29/200912/29/2009APASS
DetailsForrest France
Fire sprinkler permit final approved.
INSP-Final Inspection12/28/200912/28/200912/28/2009APASS
DetailsForrest France
Fire sprinkler permit work passed final inspection.
INSP-Final Inspection12/21/200912/22/200912/22/2009PNR
DetailsForrest France
Painted heads need replaced, riser supervision is incomplete.
INSP-Sprinkler Rough-in/Hydro12/21/200912/22/200912/22/2009APART
DetailsForrest France
Overhead hydrostatic retest passed.
INSP-Sprinkler Rough-in/Hydro12/18/200912/18/200912/21/2009AFAIL
DetailsForrest France
Overhead hydrostatic test failed due to pressue loss at the guage.
INSP-Sprinkler Rough-in/Hydro12/16/200912/17/200912/17/2009AFAIL
DetailsForrest France
Overhead hydrostatic testing failed due to pressure loss at the guage and visible leakage at two locations.
INSP-Sprinkler Rough-in/Hydro12/14/200912/16/200912/16/2009ANR
DetailsForrest France
Hydro - Contact: Todd Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley NOTE: Not ready for inspection per contractor- to be rescheduled.
INSP-Sprinkler Rough-in/Hydro12/14/200912/17/200912/16/2009ACANC
DetailsForrest France
Final - Contact: Todd Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in12/14/200912/15/200912/15/2009PFAIL
DetailsForrest France
Inspection for overhead cover at the drop ceilings in the corridors and adjacent rooms failed due to some items including missing seismic bracing, one blocked upright, two areas missing coverage, one mixed head, one upright to be relocated- see plans for red-lines.
INSP-Sprinkler Rough-in10/23/200910/23/200910/23/2009PPART
DetailsForrest France
Todd Phone#: ###-####
INSP-Sprinkler Rough-in/Hydro10/20/200910/21/200910/21/2009APART
DetailsForrest France
Overhead fire sprinkler work at the sheetrock ceiling above the reception desk is okay for cover.
INSP-Sprinkler Rough-in/Hydro10/13/200910/14/200910/14/2009APASS
DetailsTroy Cobbley
See the city approved plans for areas marked in red with todays date where the sprinkler piping can be covered.
INSP-Sprinkler Rough-in10/5/200910/5/200910/5/2009PPART
DetailsForrest France
Okayed for cover as marked on approved plan set.
INSP-Sprinkler Rough-in/Hydro9/17/20099/18/20099/18/2009APART
DetailsForrest France
Inspection for overhead cover okayed for the boy's restroom only, HVAC ducting at the girls restroom side obstructs coverage at one upright.