Permit NumberFIR09-00370
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 401 W FRONT ST Unit: 401
Project NameForum Professional Offices
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of relocating and adding sprinklers to accommodate new wall and ceiling configurations. This area is located on the north half of the fourth floor, of a six floor building. The existing system is a 2"x1½"x1¼" grid. The building has an existing 250 gpm @ 60 psi fire pump.

(FORUM PROFESSIONAL OFFICES - BELLA PLAZA OFFICE BLDG - 4th FLR) This building is fully sprinklered for allowable height and area increase. To build-out for finish and occupancy a 5,582 square foot office space of existing shell building (BLD06-00628) per approved plans and CUP05-00107 & DRH03-00228. Work includes construction of interior non-combustible, non-rated walls to create five enclosed offices, open office space, reception area, a break room, 280 square foot conference room, and a storage room, electrical, mechanical, plumbing, sprinkler & alarm systems installation; suspended ceiling grid system, cabinetry / millwork & interior finishes. Fire and Life Safety features for the entire SHELL building (BLD06-00628) SHALL be installed and approved for use by required city agencies before any portion of the building can be occupied for use. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/28/20097/29/20097/29/2009APASS
DetailsForrest France
Final walkthrough passed, fire sprinkler permit finaled.
INSP-Sprinkler Rough-in7/21/20097/22/20097/22/2009PPART
DetailsForrest France
Noted corrections verified for completion, overhead modifications okay for cover.
INSP-Sprinkler Rough-in7/20/20097/21/20097/21/2009PFAIL
DetailsForrest France
Pendent head at the storage room is overspaced, two hangers at office 412 are beyond max. spacing to heads on systems over 100 psi. See red line annotations on stamped plan set and circled items # 19 and 22 on FP1 under general notes for details.
INSP-Sprinkler Rough-in7/20/20097/20/20097/20/2009PDEFR
DetailsForrest France
Could we geet this around 3ish, Ryan is the contact at ###-####. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus