Permit Information
Permit NumberFIR09-00386
StatusFinaled
Name ALARMCO
Site Address 2390 E FREIGHT ST
Project NameWINCO DISTRIBUTION CENTER-DISP
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide sprinkler monitoring for the dispatch and maintenance out building. Also included are NAC panels for voluntary notification as well as pull stations. Devices to be added to the existing fire alarm panel located in the main building.

Associated building permit: BLD09-00168 Dispatch and Maintenance Building - To construct a new 12,395 square foot, one story with 960 square foot storage mezzanine, pre-engineered metal office and maintenance building and related site improvements. This building contains an 8,265 square foot vehicle repair bay and storage areas and a 4,130 square foot dispatch office area. All construction per the approved plans and attached comment list. DRH07-00594 JCM


NOTE TO INSPECTOR: The out-building addressable devices must have the building name in the point description. This is to ensure the quickest response for the fire department in the event of an alarm at the site since all of the buildings will list as the same address. This has been confirmed via a phone conversation with Mike at Alarmco on 6/23/09.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/12/200911/12/200911/12/2009PPASS
DetailsForrest France
Fire alarm permit finaled, corrections finished.
INSP-Sprinkler Rough-in/Hydro9/15/20099/16/20099/17/2009APART
DetailsForrest France
TOC approved.
INSP-Final Inspection9/14/20099/14/20099/14/2009PPART
DetailsForrest France
Inspection date is 9/15 as previously discussed.
INSP-Final Inspection9/9/20099/9/20099/9/2009PPART
DetailsForrest France
Corrections verified for completion, fire alarm system testing passed, XP strobes at the fuel station area are not installed.
INSP-Final Inspection9/8/20099/8/20099/8/2009PFAIL
DetailsForrest France
Seven manual pull stations are mounted too high-see fire code review note #9, two 75cd notification appliances are overspaced at the return bay, one 110cd appliance is overspaced per install and red lined note on stamped plan set- see note #1, main drain vavle at the sprinkler riser need not be supervised, explosion proof strobes at the fuel bay are missing, overspaced notification per plan review annotations at the return bay, provide "NFPA 72 Record of Inspection and Testing" per note #3, provide a lock and label at the panel circut breaker-note #8. No further testing completed at this time until repairs are finished.
INSP-Final Inspection9/4/20099/4/20099/8/2009PNR
DetailsForrest France
brian Phone #: ###-####
INSP-Final Inspection9/3/20099/3/20099/8/2009PNR
DetailsForrest France
Incompleted work on 9/3.